8.4 AUTOMATIC TUNING

3. Press Return Key for at least 6 seconds ( maximum 16 seconds). This

initializes the Auto-tune function. (To abort auto-tuning procedure

press Return Key and release).

2. Ensure Proportional Band 'Pb' is not set at '0'.

1. Ensure that controller is correctly configured and installed.

4. The Decimal point in lower right hand corner of PV display flashes to

indicate Auto-tune is in progress. Auto-tune is complete when the

flashing stops.

5. Depending on the particular process, automatic tuning may take up

to two hours. Processes with long time lags will take the longest to

tune. Remember, while the display point flashes the controller is

auto-tuning.

NOTE: If an AT error(

) occurs, the automatic tuning process

is aborted due to the system operating in ON-OFF control(PB=0).

The process will also be aborted if the set point is set to close to

the process temperature or if there is insufficient capacity in the

system to reach set point (e.g. inadequate heating power

available). Upon completion of Auto-tune the new P.I.D. settings

are automatically entered into the controller's non-volatile memory.

8.5 MANUAL P.I.D. ADJUSTMENT

8.5 MANUAL P.I.D. ADJUSTMENT

Whilst the auto-tuning function selects control settings which should prove

satisfactory for the majority of processes, you may find it necessary to

make adjustments to these arbitrary settings from time to time. This may

be the case if some changes are made to the process or if you wish to

'fine-tune' the control settings.
It is important that prior to making changes to the control settings that

you record the current settings for future reference. Make slight changes

to only one setting at a time and observe the results on the process.

Because each of the settings interact with each other, it is easy to become

confused with the results if you are not familiar with process control

procedures.

TUNING GUIDE

TUNING GUIDE

Proportional Band
Symptom

Solution

Slow Response

Decrease PB Value

High Overshoot or Oscillations

Increase PB Value

Integral Time (Reset)
Symptom

Solution

Slow Response

Decrease Integral Time

Instability or Oscillations

Increase Integral Time

Derivative Time (Rate)
Symptom

Solution

Slow Response or Oscillations

Decrease Deriv. Time

High Overshoot

Increase

Time

Deriv.

8.6 MANUAL TUNING PROCEDURE

8.6 MANUAL TUNING PROCEDURE
Step 1: Adjust the integral and derivative values to 0. This inhibits the

rate and reset action

Step 2: Set an arbitrary value of proportional band and monitor the

control results

Step 3: If the original setting introduces a large process oscillation, then

gradually increase the proportional band until steady cycling

occurs. Record this proportional band value(Pc).

Step 4: Measure the period of steady cycling

PV

PV(Process value)

Tc

TIME

Record this value (Tc) in seconds

Step 5: The Control Settings are determined as follows:

Proportion Band(PB)=1.7 Pc

Integral Time (TI)=0.5 Tc

Derivative Time(TD)=0.125 Tc

25

50

75

100

125

150

0 10 20 30 40 50 60 70 80 90

15 minutes

ON

OFF

Process Value

Alarm Output

t(minutes)

The dwell function may be used to operate an external device such

as a siren to alert when a soak time has been reached.

need to be set to the value 13. The alarm contact will now

operate as a timer contact, with the contact being open on the

initial start up. The timer begins to count down once the set point

temperature is reached. After the setting at

has elapsed, the

alarm contact closes.

9. ERROR MESSAGES

9. ERROR MESSAGES

Symptom

Cause (s)

Solution (s)

Sensor break error

Replace RTD or sensor

Use manual mode operation

Process display beyond

the low range set point

Re-adjust

value

Re-adjust

value

Process display beyond

the high range set point

Analog hybrid module

damage

Incorrect operation of

auto tune procedure

Prop. Band set to 0
Manual mode is not

allowable for an ON-OFF

control system

Check sum error, values

in memory may have

changed accidentally

Replace module. Check for

outside source of damage

such as transient voltage spikes
Repeat procedure. Increase

Prop. Band to a number larger

than 0

Increase proportional band

Check and reconfigure the

control parameters

8.7 RAMP & DWELL

8.7 RAMP & DWELL

The FDC-9090 controller can be configured to act as either a fixed

set point controller or as a single ramp controller on power up. This

function enables the user to set a pre-determined ramp rate to

allow the process to gradually reach set point temperature, thus

producing a 'Soft Start' function.

A dwell timer is incorporated within the FDC-9090 and the alarm

relay can be configured to provide either a dwell function to be

used in conjunction with the ramp function.

The ramp rate is determined by the '

' parameter which can be

adjusted in the range 0 to 200.0 C/minute. The ramp rate function

is disabled when the '

' parameter is set to ' 0 '.

B

The soak function is enabled by configuring the alarm output to act

as a dwell timer. The parameter

needs to be set to the

value 12. The alarm contact will now operate as a timer contact,

with the contact being closed at power up and opening after the

elapsed time set at parameter

.

If the controller power supply or output is wired through the alarm

contact, the controller will operate as a guaranteed soak controller.

In the example below the Ramp Rate is set to 5 C/minute,

B

=12 and

=15 (minutes). Power is applied at zero

time and the process climbs at 5 C/minute to the set point of 125

C. Upon reaching set point, the dwell timer is activated and after

the soak time of 15 minutes, the alarm contact will open, switching

off the output. The process temperature will eventually fall at an

undetermined rate.

B

B

B

C

Summary of Contents for FDC-9090

Page 1: ...User s Manual User s Manual FDC 9090 Self Tune Fuzzy PID Process Temperature Controller FDC 9090 Self Tune Fuzzy PID Process Temperature Controller ...

Page 2: ...hat a process should incorporate a LIMIT like L91 which will shut down the equipment at a preset process condition in order to preclude possible damage to products or system It is strongly recommended that a process should incorporate a LIMIT like L91 which will shut down the equipment at a preset process condition in order to preclude possible damage to products or system Copyright a August 2001 ...

Page 3: ...DESCRIPTION 4 INPUT RANGE ACCURACY 5 SPECIFICATIONS 6 INSTALLATION 8 OPERATION 7 CALIBRATION 7 CALIBRATION 8 OPERATION 8 1 KEYPAD OPERATION 8 2 FLOW CHART 8 3 PARAMETER DESCRIPTION 8 4 AUTOMATIC TUNING 8 5 MANUAL P I D ADJUSTMENT 8 6 MANUAL TUNING PROCEDURE 8 7 RAMP DWELL 6 1 DIMENSIONS PANEL CUTOUT 6 2 WIRING DIAGRAM 9 ERROR MESSAGES 9 ERROR MESSAGES In addition this instrument has functions of s...

Page 4: ...alibration data is lost you will need to return the controller to your supplier who may apply a charge for re calibration Note Do not proceed through this section unless their is a genuine need to re calibrate the controller All previous calibration date will be lost Do not attempt re calibration unless you have available appropriate calibration equipment If calibration data is lost you will need ...

Page 5: ...al parameters to be accessible at level 0 security 0 0 0 C B 10 C B 120 sec 30 sec 1 Proportional Cycle Time 0 to 120 seconds Relay Pulsed Voltage Linear Volt mA 20 1 0 Input Mode Selection 0 J type T C 1 K type T C 2 T type T C 3 E type T C 4 B type T C 5 R type T C Note T C Close solder gap G5 RTD Open G5 6 S type T C 7 N type T C 8 PT100 DIN 9 PT100 JIS 10 Linear Voltage or Current Alarm Mode S...

Page 6: ...easure the period of steady cycling PV PV Process value Tc TIME Record this value Tc in seconds Step 5 The Control Settings are determined as follows Proportion Band PB 1 7 Pc Integral Time TI 0 5 Tc Derivative Time TD 0 125 Tc 25 50 75 100 125 150 0 10 20 30 40 50 60 70 80 90 15 minutes ON OFF Process Value Alarm Output t minutes The dwell function may be used to operate an external device such a...

Page 7: ... limited to replacement or repair free of charge or refund of purchase price within the warranty period specified This warranty does not apply to damage resulting from transportation alteration misuse or abuse Future Design Controls warranties or representations of any sort regarding the fitness for use or the application of its products by the Purchaser The selection application or use of Future ...

Reviews: