Section 50
00-02-1031
2019-08-07
- 23 -
State Timer Setup Screen
User may edit all state timers if marked in use. State 1
–
Panel Ready and 23
– Shutdown are Read Only and
cannot be edited. The states used for a given application
are configured by the Centurion Configuration Tool
software.
When the state timeout value is reached, the state logic
proceeds to the next In Use state. A state timeout may also
be configured to trigger a fault event such as a prelube
permissive failure; however, the operation depends on the
configuration.
Maintenance Timer Setup Screen
The user may access and edit the ten (10) maintenance
duration presets and time remaining settings, if used by the
configuration. All maintenance timer units are in hours.
NOTE:
These are configured by the Centurion
configuration tool software and must be manually
initialized in Centurion display.
When the timer reaches 0 hours an event may be
configured to alarm or generate a message event that
maintenance is required.
Start / Restart Maintenance Timers
To initialize or restart the timers, position cursor on TIME
REMAINING and press the reset key.