Miscellaneous Setup Screen
a) Core/Expansion Flywheel Teeth:
Engine:
Define a value for flywheel teeth (Pulses Per
Revolution) used to calculate RPM.
Motor:
When setpoint set to zero, crank attempts becomes
# of starts per hour (Short cycle limit) for electric motor
applications.
b) Hour Meter (0.0-499999.9):
Reset or preset the internal
hour meter.
c)
Crank Attempts (1-16):
Engine: Define a value for number of crank attempts after
which an over-crank sequence signal will be triggered in the
system. If the configuration includes an Overcrank event, it
will be triggered by this signal.
Motor: Define a value for number of motor start attempts
per hour after (Short cycle) which an excess start attempts
will be triggered in the system. If the configuration includes
an Overcrank/Excess starts event, it will be triggered by this
signal.
WARNING: The following cold temperature offset
values should only be adjusted by personnel with a full
working knowledge of the Centurion in conjunction
with calibrated reference equipment.
h) Core CJ Temp:
Enter a non-zero value for temperature
adjustment in tenths of a degree to offset the temperature
readings.
i) Exp CJ Temp Offset:
Enter a non-zero value for
temperature adjustment in tenths of a degree to offset the
temperature readings.