background image

-1-

M

VIEW™

 

Series

 

J1939

 

Module

 

Phone: +1 (918) 957-1000

Bulletin No. MVJ1939-A

Fax: +1 (918) 957-1075

Drawing No. LP1084

www.fwmurphy.com

Effective 2018-11-30

FOR USE IN HAZARDOUS LOCATIONS:
    Class I, Division 2, Groups A, B, C, and D
    T4

C

US

UL

R

LISTED

IND.CONT. EQ.

E317425

CONFIGURED USING M-VIEW DESIGNER 3.1

DIGITALLY ISOLATED J1939 PORT CAPABLE OF 
COMMUNICATING WITH ANY J1939 DEVICE

POWERED AND CONFIGURED FROM M-VIEW HOST DEVICE

BUILT-IN TERMINATION RESISTOR SELECTABLE THROUGH A 
SWITCH

C

US LISTED

UL

R

IND. CONT. EQ.

E302106

II 3 G Ex nA IIC T4 Gc
-40°C 

 T

AMB

 

 75°C

DEMKO 14 ATEX 1387X
IECEx UL 15.0035X

GENERAL

 

DESCRIPTION

 

The MV-J1939 is a J1939 communication module designed for use

with CAN enabled devices using J1939 protocol. The module provides
the M-VIEW a J1939 communications port. It is built with digital isolation
to protect the M-VIEW from the J1939 bus and vice versa. It provides the
ability to communicate to any J1939 device. The MV-J1939 module has
a termination resistor built-in, and is selectable through a switch. The
connector is pluggable for easy removal of the MV-J1939 module from
the J1939 bus, without disturbing communications with other devices on
the bus.

The modules connect and communicate via proprietary USB

connection to the various M-VIEW devices. The M-VIEW devices,
equipped with serial ports as well as Ethernet port(s), allows the system
to share data with PCs, PLCs and SCADA systems. The maximum
number of modules varies for each M-VIEW device, see specific model
for details. Remove power from the host device before installing or
replacing any modules.

CONFIGURATION

The M-VIEW is configured with Windows

®

 compatible M-VIEW

DESIGNER 3.1 software. The software is an easy to use, graphical
interface which provides a means of configuration and commissioning of
new systems, as well as routine module re-calibration.

SAFETY

 

SUMMARY

All safety related regulations, local codes and instructions that appear

in this literature or on equipment must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment
connected to it. If equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired. 

Do not use this unit to directly command motors, valves, or other

actuators not equipped with safeguards. To do so can be potentially
harmful to persons or equipment in the event of a fault to the unit.

ORDERING

 

INFORMATION

A listing of the entire M-VIEW family of products and accessories can be 
found at 

www.fwmurphy.com

.

4.65

(118)

2.80 (71)

1.25 (32)

DIMENSIONS

 

In

 

inches

 

(mm)

DESCRIPTION

PART NUMBER

M-VIEW Module, J1939 Protocol Interface

50704942

WARNING - EXPLOSION HAZARD - DO NOT D
EQUIPMENT UNLESS POWER HAS BEEN SW
OR AREA IS KNOWN TO BE NON-HAZARDOU

CAUTION: Risk of Danger.

Read complete instructions prior to installation 
and operation of the unit.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 
DIVISION 2.