Section 50
00-02-0271
2018-10-23
-
6 -
Typical Hazardous Areas Installation
WARNING: FOR HAZARDOUS APPLICATION REQUIREMENTS, THE
S1501 COMPLETE SYSTEM MUST BE INSTALLED IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE (NEC) CLASS I, DIVISION
1, GROUP D (ARTICLE 504) SPECIFICATIONS. SENSOR INPUT
WIRES MUST BE SEPARATED A MINIMUM OF 2 IN. (51 MM) FROM
OTHER WIRES. USE OF SENSOR INPUT WIRE TYPE CONDUIT IS
RECOMMENDED.