background image

D1033 

- SIL 2 Switch / Proximity Detector Repeater Transistor Output 

ISM0043-15 

D1033D - D1033Q 

INSTRUCTION & SAFETY MANUAL 

SIL 2 Switch/Proximity Detector 

Repeater Transistor Output 

DIN-Rail Models D1033D, D1033Q 

Summary of Contents for D1033Q

Page 1: ...033 SIL 2 Switch Proximity Detector Repeater Transistor Output ISM0043 15 D1033D D1033Q INSTRUCTION SAFETY MANUAL SIL 2 Switch Proximity Detector Repeater Transistor Output DIN Rail Models D1033D D103...

Page 2: ...ms to 7113 22782 5 78 I 60079 15 T V Certificate No C IS 236198 03 SIL 2 conforms to IEC61508 2010 Ed 2 T V Certificate No C IS 236198 09 SIL 3 Functional Safety Certificate conforms to IEC61508 2010...

Page 3: ...d in standard version D1033 Transistor Output for fault detection on dual channel version Line fault detection with common signalling available when using Power Bus enclosure Three port isolation Inpu...

Page 4: ...Voltage free Contact Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact Input Ch 2 for Proximity Input Ch 2 for Voltage free Contact Input Ch 2 for Proximity Input Ch 2 for Voltage free C...

Page 5: ...iated Apparatus excluding the cable then 50 of Co and Lo parameters are applicable and shall not be exceeded 50 of the Co and Lo become the limits which must include the cable such that Ci device C ca...

Page 6: ...N HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1033Q 13 14 3 4 1 2 Common Channels 1 3 Supply 24 Vdc Out 1 5 6 Common Channels 2 4 Out 2 7 Out 3 8...

Page 7: ...fety Function dd du sd su 142 61 MTBF safety function one channel 1 tot safe MTTR 8 hours 800 years no effect No Effect failures 116 69 not part Not Part failures 218 50 tot device Total Failure Rate...

Page 8: ...rs no effect No Effect failures 127 75 not part Not Part failures 370 70 tot device Total Failure Rate Device tot safe no effect not part 645 40 MTBF device one channel 1 tot device MTTR 8 hours 176 y...

Page 9: ...s or Hazardous Classified Locations Class I Division 2 Groups A B C D T Code T4 Class I Zone 2 Group IIC IIB IIA T Code T4 FM Approved under Entity Concept or third party approval Hazardous Classified...

Page 10: ...ed from each other and do not produce any unintentional connection Connect SPST output transistors checking the load rating to be within the maximum rating 100 mA 35 V resistive load The enclosure pro...

Page 11: ...with terminating line resistor ON CH2 Setting Line fault detection ON IN OUT Operation NO NC or NC NO NO NO or NC NC ON OFF Disabled contact proximity sensor Enabled proximity sensor or contact with t...

Page 12: ...Output Input Output Output Input Output Input 9 NO 10 OR NC 9 10 9 NO 10 OR NC 9 10 7 NO 2 NC 7 2 7 NO 2 NC 7 2 Input Output Input Output Output Input Output Input 11 NO 12 OR NC 11 12 11 NO 12 OR NC...

Page 13: ...ut Input Output Output Input Output Input 13 NO 14 OR NC 13 14 13 NO 14 OR NC 13 14 1 ND 2 NE 1 2 1 ND 2 NE 1 2 ND Mode NC Mode No Fault No Fault 7 ND 2 NC 7 2 Switch 4 positions Input Output Input Ou...

Page 14: ...utput Input Output 15 NO 16 NC 15 16 8 NC 6 NO 8 6 Switch 8 positions Input Output Input Output 15 NO 16 OR NC 15 16 8 NO 6 NC 8 6 ON Switch 8 positions OFF Switch 8 positions OR Switch 4 positions Sw...