14
5.6 Turn Off the UPS:
(1) In Inverter Mode:
Press “OFF” button continuously for more than 1 second to turn off
the UPS. Then the UPS will get into self-test status first. After
having finished the self-test, the UPS will get into no output or
bypass mode. At this time, the UPS might has output if bypass is
enabled. Disconnect the utility power to turn off the output.
(2) In Battery Mode:
Press “OFF” button continuously for more than 1 second to turn off
the UPS. Then the UPS will get into self-test status first. After
having finished the self-test, the UPS will be turned off completely.
NOTE
:
:
:
:
In emergency situation, the UPS can be shutdown by
taking off the EPO cover on the rear panel of the UPS. When
you want to turn on the UPS, you should restore the cover
firstly.
5.7 Audible Alarm Mute Function:
If the alarm is too annoying in battery mode, you may press “ON”
button continuously for more than 1 second to clear it. Moreover, the
alarm will be enabled when the battery is low to remind you to
shutdown the load soon.
5.8 Operation Procedure of External Battery for Long
Backup time Model (“S” Model)
The units with CE markings—
1) Use the battery pack with voltage: 36VDC for 1KS (6 pcs of 12V
batteries paralleled as 2 teams), 96VDC for 2KS/ 3KS (8 pcs of
12V batteries) 240VDC for 6KS(20pcs of 12V batteries).
Connection of batteries more than or less than required will cause
abnormality.
Summary of Contents for AP160LCD
Page 1: ...USER S MANUAL MANUALE UTENTE For Models AP160LCD 1 6KVA Uninterruptible Power System...
Page 33: ...30 Appendix Back View of 1K S Back View of 2K Back View of 2KS 3K S...
Page 34: ...31 Back View of 6K S Battery pack for 1 3KS Battery pack for 6KS...
Page 35: ...32 614 00652 01...
Page 36: ...33 MANUALE DELL UTENTE Modelli AP160LCD 1 6KVA Gruppo di continuit UPS...