Usage of Keys:
To enter in the function menu for modification or to come out from the function
menu/submenu.
Up Key is used to increment the parameter value. It is also used to go to the next
parameter/sub-menu.
Down Key is used to decrement the parameter value. It is also used to go back to
the last parameter/sub-menu.
To store the parameter value and use to enter in the function for modification.
6.1
C
ONFIGURABLE ITEM
Table 6 Configurable item
Channel Configuration Parameter
Alarm on
delay
Delay time, after which the buzzer will be activated
Alarm off
delay
Delay time, after which the buzzer will be activated
Set point
High
The upper limit of value, after which buzzer and ALH LED will be
blink.
Set point
Low
The lower limit of value, after which buzzer and ALL LED will be
blink.
Unit
There are 8 pressure units available in this device.
Offset
A small correction may be required when actual sensor is
connected to the Pressure device. This is a mathematical value
which is directly added to the reading.
Multiplier
A value to remove any scale error. This is a mathematical value
which is directly multiplied to the reading.
Displayed reading = (reading x multiplier) + offset