Page. 37
LM P RS485 Data Logger
T
ROUBLESHOOTING GUIDE
Table 9 Troubleshooting guide
Note: if you face any other problem, please contact G-Tek Corporation Pvt. Ltd.
PROBLEM
CORRECTIVE ACTION
How to get the status
of the batch (running
or not)?
•
Note the STR LED status on display. The STR LED will be
blinking at every 1 second interval.
•
The user can also see the status from menu for batch
operation, it will show stop option.
How Alarm condition is
shown on display?
•
ALL (Alarm Low) or ALH (Alarm High) LED will be ON
according to alarm high/low condition.
If LED display is Blank,
then what should be
done?
•
Check if power supply adapter is properly connected to the
device.
•
Also check if adapter is faulty or not.
•
Check power supply polarity is proper or not.
Why Display shows
“
undr
” / “
over
”?
•
If the pressure input goes out of range of then display shows
“
undr
” / “
over
” on display.
How to acknowledge
Buzzer?
•
Buzzer is acknowledged by pressing UP and ENTER keys
simultaneously. Buzzer will be silent for Alarm OFF time delay
(AOFT).
How to give Zero Offset
or how to remove
offset value at zero
condition?
•
At zero condition (open condition), if any value shows on
display, user can remove this offset value by pressing a
FUNCTION ,DOWN and ENTER keys at the same time.
How to change the unit
of the pressure input?
•
Follow the steps given in
. After selecting the
required unit , its corresponding unit LED will be ON and
pressure reading on display will be in that unit.
How to change the
baud rate and parity of
the device?
•
For changing the baud rate and parity, the user needs to enter
in communication menu using password(refer
that , if the batch is in running condition then the baud rate and
parity cannot be changed.
What is the procedure ,
if user forgets
password?
•
No, there is no such procedure to reset password, in this
situation contact factory immediately.
Why the RTC is not
updated?
•
If RTC battery is drained and power is off for some time period,
then it can be possible that RTC might not work.
•
Check the RTC battery voltage.
What to do if device
does not communicate
with remote software?
•
Check the baud rate ,parity and device address of the device is
selected properly.
•
Check the RS485 connection( twisted pair polarity ) and cable
continuity .
Summary of Contents for LM Pro 63 Series
Page 1: ......