6.4.1 ASH (Alarm Set Point High)
In this menu, Alarm setpoint High along with its alarm delay can be seen,
which is Preset at +8°C
and 10 hours. User can only view this parameter.
Alarm ON Time duration for Setpoint High is in HR:MN
#
. This is the time required for the reading
to remain more than ASH, to be treated as alarm.
Figure 11 Alarm Set Point High
6.4.2 ASL (Alarm Set Point Low)
In this menu, Alarm setpoint Low along with its alarm delay can be seen, which is
preset at -0.5
°C and 1 hour.
User can only view this parameter.
Alarm ON Time duration for Setpoint Low is in HR:MN
#
. This is the time required for the reading
to remain more than ASL, to be treated as alarm.
Figure 12 Alarm Set Point Low
In alarm high/low condition after Alarm ON High/ Low delay, the buzzer will be activated for 1
sec at every 1 hour interval. For detailed buzzer operation refer