38
7.3.9.2
Range Low
This feature is used for selecting the minimum value of the display that should be displayed on the led
display or is measured by the sensor.
For example:
If the user wants to measure the percentage of pressure of gases in the pressure valve, then then user
needs to display the output in range of 0 to 100 %. So, here the range low must be set as 0 by the user.
Now, for the above case if the user wants to just measure the percentage of pressure if gone above
50% that is 50-100% then in this case the user must set the value of range low as 50.
User can set the range low values anywhere between -3276.8 to 3276.7.
To set the Range Low for a channel then follow the procedure shown in figure- 39 by pressing the
appropriate buttons given in the front panel of the LmNet.
7.3.9.3
Span
Span is the total range of values that a user wants to measure.
Span value indicates the total interval of which all the output values will be displayed.
Press up key and down key
to change the value
0
rAngE Lo
SAvE
1 128.55
Figure 38 Sensor Selection
Figure 39 Range Low selection
U 1voLt
bI 1voLt
SAvE
SAvE
U 5voLt
bI 5voLt
SAvE
SAvE