57
4.5 Relay outputs
Signal contact 1 ("Locked by motor" position reached)
Signal contact 1 (terminal 41 and 51) closes as soon as the motor-driven shoot-bolt lock has reached
its initial position. During this process, the latch and deadbolt triggers are retracted and the top and
bottom locking move to the locked position. The actual automatic locking operation of the passive
leaf is only performed once the passive-leaf control lock B 1895 has been triggered by the closing
door leaf.
Signal contact 2 ("Unlocked by motor" position reached)
Signal contact 2 (terminal 42 and 52) closes as soon as the shoot-bolt lock has been fully unlocked by
the motor (release of active and passive leaf).
Deadbolt monitoring (only with B-2393x)
The deadbolt monitoring signal is output potential-free via the deadbolt monitoring relay contact
(terminal 43 and 53) as soon as the deadbolt of the active leaf lock engages in the shoot-bolt lock.
If the deadbolt monitoring is actuated when the deadbolt is moved manually to the locked position
(with B-23xxx), control signals are not processed at the inputs I1 and I2. This means that the door
cannot be unlocked by the motor. The controller displays "S".
Latch (latchbolt) monitoring
The latch or latchbolt monitoring signal is output potential-free via the latch(bolt) monitoring relay
contact (terminal 44 and 54), as soon as the latch or latchbolt of the active leaf lock engages in the
shoot-bolt lock.
Fig.16: Installation
41 51 42 52 43 53 44 54
Summary of Contents for B-54900-01-2-8
Page 141: ...141 ...
Page 143: ...143 1 2 3 4 ...
Page 146: ...146 B 2193x B 2393x 06 2019 22288S Designed in Germany Notizen Notes Notes Notas ...
Page 147: ...147 Notizen Notes Notes Notas ...