57
Blink code
Problem
Cause
Help
Sensor "Unlocked" po-
sition of active leaf not
reached
y
y
Load on active leaf too
high
y
y
Check whether the
door leaf or door
frame is twisted or
warped
y
y
Insufficient power in
power supply unit
(see point 2.2)
y
y
Foreign object in the
lock
y
y
Check the lock for
foreign objects
Sensor "Unlocked" posi-
tion not fully reached
y
y
Sensor connected
incorrectly
y
y
Connection cable
defective
y
y
Check wiring
(BK, GY, WHGN)
y
y
Load on passive leaf
too high
y
y
Check whether the
door leaf or door
frame is twisted or
warped
y
y
Insufficient power in
power supply unit
(see point 2.2)
y
y
Foreign object in the
lock
y
y
Check the lock for
foreign objects
Critical error
y
y
Test run not carried
out
y
y
Perform test run
(see point 3.2 or 6)
y
y
Test run not
completed
successfully
y
y
Open door leaf for
test run and hold open
y
y
Eliminate error as indi-
cated by blink code
Then repeat test run in
each case (see point 6)
y
y
"Locked" position
not reached
2x consecutively
y
y
Check the lock for
foreign objects
y
y
Load on door system
too great
Motor error
y
y
Lock blocked
y
y
Replace lock
Programming mode
active
y
y
Service plug not
removed
y
y
Exit programming
mode (see point 6.2)
Once the error has been eliminated, the blink codes in the controller must be acknowledged
(see point 6.3).
Summary of Contents for BKS B-1893 Series
Page 31: ...31 ...
Page 131: ...131 ...
Page 133: ...133 1 2 3 4 ...
Page 135: ...135 A 3 Profilfräsung A 3 Profile cutout A 3 Fraisage du profilé A 3 Fresado del perfil ...
Page 136: ...136 B 1893x B 1993x 10 2017 20734ES Designed in Germany Notizen Notes Notes Notas ...
Page 137: ...137 Notizen Notes Notes Notas ...
Page 138: ...138 B 1893x B 1993x 10 2017 20734ES Designed in Germany ...
Page 139: ...139 ...