52
Multi-point locks electrically couplable or with monitoring contacts
Installation instructions
SECURY 19 EK | 19 EK EVP | 19 S | 19 S EVP
04.2016 | G31347 | Designed in Germany
DE
EN
FR
ES
4.1.2 SECURY 1975
Make sure that the power supply to the multi-point lock exists.
Make sure that the multi-point lock is electrically decoupled (no control
signal).
Release the lever handle so that it returns to its initial position.
Check whether the three latchbolts are projected automatically and
completely through pressing on the trigger lever.
Only for SECURY 1970 / 1970 EVP (Multi-point lock for 1-leaf doors):
Make sure that all three latchbolts are completely projected.
Check through pressing on the latchbolts (max. 20 N) whether they are
secured against being forced back.
In the decoupled status (no control signal), couple in the outside lever
handle using the locking cylinder / cylinder cam.
Check whether all latchbolts are completely pulled back when the
outside lever handle is actuated.
Check whether the inside and outside lever handles can be pressed down
easily.
Now decouple the outside lever handle again using the locking cylinder /
cylinder cam. The outside lever handle must have no function now (idle).
Couple the outside lever handle in electrically.
Check whether all latchbolts are pulled back when the outside lever
handle is actuated.
Now decouple electrically the outside lever handle again. The outside
lever handle must have no function now (idle).
Separate the multi-point lock from the power circuit.
Operating current (fail-secure) version:
Check whether the outside lever handle is decoupled (idle).
Quiescent current (fail-safe) version:
Check whether the outside lever handle is coupled in.
Make sure that, after the test, all latchbolts are pulled back, i.e. all
latchbolts are in the initial position.