8 MAINTENANCE
Gabarrón electric boilers do not need any special maintenance, only the following should be checked:
-Check the pressure indicated by the pressure gauge frequently, ensuring that it is between 1 and 1.5 bar when cold.
- Never start the boiler when it is empty.
- Never start the boiler when the S.H.W. tank is empty; to fill it for the first time open a hot water tap and wait until
water comes out of it.
-Precaution against freezing. In dwellings that are frequently unoccupied or at risk of freezing, an anti-freeze of the
appropriate quality can be added to the water of the heating installation – the concentration must not exceed 30%
in volume.
- Clean the surfaces of the boiler with a damp cloth, having previously disconnected it from the mains. Do not use
solvents or abrasive products.
9 TROUBLESHOOTING
Problem
Possible cause
Solution
Boiler will not start
No current entering boiler.
Check the installation.
Overheating of the heating.
See Section 7.3.4.
Overheating of S.H.W.
See Section 7.4.2.
S.H.W. tank empty.
Open a hot water tap until the water
flows.
Error E1
Heating water out temperature
probe defective.
Contact Technical Service
Error E2
Heating water return temperature
probe defective.
Contact Technical Service
Error E3
Lack of heating water flow.
Pump blocked.
Unblock – see instructions
Valves shut.
Open valves.
Air in the installation.
Purge the installation
Error E4
Pump blocked.
Unblock – see Section 7.3.3.
Valves shut.
Open valves.
Air in the installation.
Purge the installation.
Error E5
Configuration error of the maximum
limited output.
See Section 6 LIMITATION OF
OUTPUT
Error E6
S.H.W. temperature probe
defective.
Contact Technical Service
Heating safety valve expels water
Excessive pressure in cold.
Adjust to between 1 & 1.5bar.
Expansion vessel breakdown.
Change.
Water entering heating circuit.
Check filling valve.
S.H.W. safety valve expels water.
Entering water pressure too high.
Install a pressure reducer.
S.H.W. expansion vessel breakdown
Change.
The buttons do not respond
Control panel blocked
See Section 7.2 BLOCKING THE
CONTROLS
Low temperature in the installation.
Heating setting low.
Regulate.
Setting of ambient thermostat low.
Regulate.
Resistances broken down.
Contact Technical Service.
Badly calculated installation.
Increase output.