SYC6714

Synchronizer

1

Overview

GENERATOR AND MAIN BUS AC INPUT

Sensitivity

50 V RMS - 500 V RMS 

(line-to-line or line neutral)

Frequency

50 or 60 Hz nominal 

Isolation

1000 V minimum

Burden

less than 2.5 V A

BATTERy/DC POwER SUPPly REqUIREMENTS 

(TERMINAlS 8-10)

Low Voltage Range 

(Terminals 8 & 9 connected) 

10 - 16 V DC 

High Voltage Range

14 - 40 V DC

Current Required

less than 200 mA

PERfORMANCE (wITh 

ESD SERIES

)

Capture Range

+4% based on 3250 Hz

Output Voltage

3 - 7 V DC

Breaker Closure Window Angle

1 ° - 25 °

Relay Contact Rating 

(N.O. or N.C.)

10 A @ 28 V DC

Phase Error Adjust Range

+/- 10° typical

2

SpeCifiCatiOnS

ENvIRONMENTAl

Temperature Range

-40 to +180° F [ -40 to +85°C]  

Humidity

 up to 100 %

Vibration

5g (20 – 200 Hz)

Case

Corrosion resistant and fungus proof IP22 

with terminal cover in place

PhySICAl

Dimensions

 5.72 [146] x 7.03 [179]  x 1 in [25] 

Weight

1.5 lb [0.68 kg]

Mounting

any position, vertical preferred

The GAC SYC6714 accessory module adjusts a speed control unit to 

obtain an equal AC phase relationship between the generator and the 

main bus (mains).  When paralleling a synchronous generator to a main 

bus, generators, or utility. 

The SYC6714 provides the SYNC CHECK function which activates a 

relay to connect the generator to the main bus. Typically this takes less 

than 3 seconds when the generator sets are at rated speed and using 

optimum speed controller performance settings.

The GAC SYC6714 is a CE (Community Europe) approved unit the 

installation requirements must be met to maintain EMC capabilities. 