background image

Pub.  42004-451A 

Model 13314-004 Div. 2 Hazardous Area 100-Volt Horn Driver 

Page:  

2 of 4

 

f:\standard ioms - current release\42004 instr. manuals\42004-451a.doc 

05/11 

Figure 2.  Typical Installation 

The installation of this speaker assembly must conform to regulations governing electrical equipment for 
hazardous locations and provisions of the National Electrical Code. 

Install the mounting assembly and the horn, then complete the following instructions to install the driver 
onto the horn. 

Wiring Instructions 

Refer to the following chart to determine the appropriate gauge speaker cable. 

Cable Options 

Distance of Cable 
Run in Feet 

No. 18 AWG 

8,900 

No. 16 AWG 

14,000 

No. 14 AWG 

22,500 

Field wiring to the driver must be made using the attached three-conductor type SO cord.  Connect these 
wires as follows: 

Green:

 earth ground

Black:

 amplifier 100V + terminal

White:

 amplifier 100V 

 (com) terminal

The horn driver is factory-connected for 30-watt tap setting.  If no wattage tap changes are required, 
screw the driver assembly onto the rear of the horn as shown in Figure 2. 