background image

 

18 

 

To cool the heating system to the room temperature;  

 

To  draw  off  20 liters of water from the system, to dissolve a dose of the 

“Galan-Protektor” in this volume of water (1,5 liters of inhibitor per 100 liters 

of water), to  stir carefully, and to fill the heating system with this mixture 

through the drain valve by means  of the “Malysh” type  pump.  Draw off  20 

liters of water from the system once again and fill the hating system with 

water without inhibitor. Perform these tasks up to the complete filling of the 

heating system with mixture of water and inhibitor. For washing the system it 

is necessary to keep it working through 6 days with the temperature of the 

return pipe of +35

º

 C. During this period the washing of the system and the 

corrosion protection (inhibition) of the external surfaces of the system take 

place. At this time it is necessary to clear the filter periodically. 

After six days of operating the heating system it is necessary: 

 

To disconnect the heating system from the power network; 

 

To cool the heating system to the room temperature; 

 

To draw off water from the heating system completely. 

This water cannot be reused. If required, the procedure can be repeated. It is 

necessary to examine and check the tightening of the bolted and electrical connections, and 

the reliability of grounding connection. 

 

Boiler repair 

Remove the boiler from the heating system. Remove the electrode group (electrode) 

from the boiler case. Decontaminate the internal surfaces of the boiler.  Be convinced of 

absence of any defects. 

It is necessary to perform the following tasks in the course of the boiler repair: 

 

Remove an electrode (of the single-phase electrode boiler) or electrode group 

(of the three-phase electrode boiler) from the boiler case. Electrode or 

electrode group should be inspected for absence of defects (cracks of the 

bushing insulators, etc.) and for evaluation of electrodes wear. In case of a 

wear comprises more than 40%, the electrode (electrodes) should be 

replaced. Traditionally, this happens every 3-5 years. 

 

Clean the mating surfaces carefully for providing leak resistance  which is 

achieved by applying sealing materials in the course of the boiler assembly 

and its further operation. 

 

Give the internal surfaces of the boiler case a mirror-like polish. The internal 

surfaces should be inspected for absence of defects (such as point corrosion, 

etc.). 

 

Assemble the boiler.  The boiler assembling should  be performed with 

scrupulous attention to alignment between electrodes and to alignment 

between electrodes and the boiler case. By this is meant that equal spacing 

should exist between electrodes and between electrodes and the boiler case. 

Exclude the ingress of contamination into the boiler in the course of the boiler 

assembling. Check leak resistance of the boiler.  

Install the boiler only vertically into the heating system. Fill the heating system with 

heat-transfer agent. The surge tank should be one-thirds full of the heat-transfer agent. 

On completion of the tasks listed above it is necessary to check leak resistance of the 

heating system, tightening of the bolted and electrical connections, reliability of grounding 

connection, value of the electric resistance of grounding, and reliability of automatics. 

Perform a trial start of the heating system. Correct the detected malfunctions as may be 

required. 

A person responsible for performing these tasks should make an entry in the List of 

the performed maintenance functions, assure it by his own signature and by the seal of the 

firm (organization) and to write the address and license number of the firm (organization) 

(Appendix No. 2). 

 

“Galan-Potok” low-freezing liquid as a heat-transfer agent 

In this case the preventive maintenance of the boiler is performed one in every three 

years between the cold seasons. The examination and checking of the tightening of the 

Summary of Contents for Ochag-2

Page 1: ...OCHAG GEYSER VULKAN ELECTRODE BOILERS OPERATION MANUAL...

Page 2: ...d by the Firma Galan Joint Stock Company 11 Filling the heating system with heat transfer agent 15 Correcting procedure 16 Preventive maintenance Washing of the heating system 17 Visual examination of...

Page 3: ...ocess of installation of the heating system and boilers and in the course of starting further operation and usage of the electric boilers we convincingly ask you to familiarize yourself attentively wi...

Page 4: ...he Independent Noncommercial Organization on Certification of the Electrical Products 109052 Moscow ul Nizhegorodskaya 29 Voluntary certification Technical characteristics of the boilers produced by t...

Page 5: ...technical characteristics can slightly differ from characteristics resulted in the table above Boilers construction Depending on the boiler power the electrode boilers produced by the Firma Galan Join...

Page 6: ...ation compact size and light weight For example the weight of the boiler the power of which is equal to 6 kW comprises 1 1 kg and the weight of the boiler the power of which is equal to 25 kW comprise...

Page 7: ...automatic control system The electrode boiler cost does not include a cost of the automatic control unit With the exception of the operation manual for electromechanical model of the automatics which...

Page 8: ...the boiler and heating system including metal pipelines for the cold return pipe and hot heat transfer agent should be grounded The place of entering of the conductors into the building or constructio...

Page 9: ...rical installation of the boilers and automatics Three phase electrode boilers are connected to the four wire three phase power network the voltage of which is equal to 380 V Industrial frequency of t...

Page 10: ...unning on solid liquid or gas fuel Legend Laid on thermostat sensor Valve Filter mechanical mud settler Heat transfer agent drain valve Air drain valve Circulation pump power 70 or 100 W A Vertical se...

Page 11: ...on the basis of the specific situation the following temperatures are set on the Navigator temperature regulator Temperature on the outlet of the boiler a value belonging to the recommended optimal o...

Page 12: ...eak sensor water flooding sensor etc The Galan GSM cellular monitoring system of the heating equipment is used in conjunction with the Navigator control unit Perform the installation in accordance wit...

Page 13: ...ipping contactor size 2 up to 32 A 2 1 Automatic tripping contactor coil 220 V 2 2 Thermal relay contacts normally closed 3 Inlet temperature sensor laid on bimetallic thermostat 4 Outlet temperature...

Page 14: ...tic tripping contactor size 2 up to 25 A size 3 up to 40 A 2 1 Automatic tripping contactor coil 380 V 380 V 2 2 Thermal relay contacts normally closed 3 Inlet temperature sensor laid on bimetallic th...

Page 15: ...used for inhibition of corrosion and for scale dissolving The application of low freezing liquid saves from danger of unfreezing the heating system in the event of sudden power supply disconnection A...

Page 16: ...illed in the heating system Stir the dose of the salt solution and the water drawn off from the heating system carefully This mixture is filled in the heating system through the drain valve by means o...

Page 17: ...ost careful control over the boiler s automatic switching on and switching off It is inadmissible to switch on the boiler at presence of the frozen heat transfer agent in the system or in danger of fr...

Page 18: ...acks of the bushing insulators etc and for evaluation of electrodes wear In case of a wear comprises more than 40 the electrode electrodes should be replaced Traditionally this happens every 3 5 years...

Page 19: ...ed b Low freezing liquid as a heat transfer agent Add distilled water clear uncontaminated filtered rain water or snow melt water water the specific electric resistance of which significantly exceeds...

Page 20: ...and lubricating oils gasoline acetone turpentine bitumen roll roofing kerosene oils in the premises where the boiler is installed To dry clothing on the electric boiler shell Transportation and storin...

Page 21: ...e air locks 4 In due course the boiler wastes its power gradually under condition of using fresh water Presence of contamination rust and scale on the electrodes and on the internal surfaces of the bo...

Page 22: ...__________ _____ Performed tasks Executor Owner last name name and surname signature Name of the company performing the warranty repair Place of the seal Post and signature of the director of the com...

Page 23: ...__________ _____ Performed tasks Executor Owner last name name and surname signature Name of the company performing the warranty repair Place of the seal Post and signature of the director of the com...

Page 24: ...ce functions Date description of the maintenance functions License number address signature of the person responsible for performing maintenance functions Seal of the company organization which has pe...

Page 25: ...ery and sale certificate The electrode boiler meets the requirements of the Technical Specifications TS No 3468 001 17289826 02 Date of issue Seal of the Quality Department Sold Date of sale Place of...

Page 26: ...9 196 04 40 196 04 41 123098 Moscow m Shchukinskaya ul Marshala Novikova 2 building 1 http www galan ru e mail office galan ru MAXIMUM WARMTH MINIMUM COSTS OUR COMPANY PERFORMS THE DESIGNING INSTALLAT...

Reviews: