Base Block
base.galileosky.com/articles/#!en-documentation/base-block-user-manual
11/28
Ranges for
response/
nonresponse areas
(logical 1 and 0)
To process discrete signals,
response/nonresponse range should be
set where signals are equal to one and
zero. Discrete inputs states should be
seen in the Status of Inputs field, but not in
the Input voltage field.
While counting pulses or frequency, it is
necessary to put the value equal to half
the pulse value into all the fields of the
given group (example: the pulses'
amplitude is 5000 mV, so all the fields
must take the value 2500 mV)
Pulse count
In case of a renewable counter the maximum pulse number can be 65535, after that the
number is reset to zero.
Mean value and discrete event generation
Example 1.
Let us consider the example with the following zero input setting (see the left-hand figure:
Filter type is 0;
Filter length is 5;
Logical one zone range is 8-33V;
Logical zero zone range is 0-3V.