Before you begin

2.1  Shipment contents

Check the shipment contains the following items:

• 

1 x Gallagher T15 Reader facia assembly

• 

1 x Gallagher T15 Reader bezel

• 

1 x M3 Torx Post Security screw

• 

2 x 25 mm No.6 self tapping, pan head, Phillips drive fixing screws

• 

2 x 40 mm No.6 self tapping, pan head, Phillips drive fixing screws

2.2  Power supply

The Gallagher T15 Reader is designed to operate over a supply voltage of 13.6 Vdc measured 

at the reader terminals.  The operating current draw is dependant on the supply voltage at the 

reader.  The power source should be linear or a good quality switched-mode power supply.  The 

performance of the reader may be affected by a low quality, noisy power supply.

2.3 Cabling

The Gallagher T15 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm

2

) stranded 

security cable.  This cable allows the transmission of data (2 wires) and power (2 wires).  When 

using a single cable to carry both power supply and data, both the power supply voltage drop 

and data requirements must be considered.

 

HBUS cabling topology

The HBUS communications protocol is based on the RS485 standard and allows the reader to 

communicate over a distance of up to 500 m (1640 ft).

The cabling between HBUS devices should be done in a "daisy chain" topology, (i.e. A "T" or 

"Star" topology should not be used between devices).  Should "Star" or "Home-Run" wiring be 

required, the HBUS 4H/8H Modules and the HBUS Door Module allow multiple HBUS devices to 

be individually wired to the one physical location.

The end devices on the HBUS cable should be terminated using 120 ohms resistance.  To 

terminate the Gallagher Controller 6000, connect the supplied on-board termination jumpers 

to the Controller.  To terminate a reader, connect the orange (termination) wire to the green 

(HBUS A) wire.  Termination is already included at the HBUS Module, (i.e. each HBUS port is 

permanently terminated at the module).

Summary of Contents for C300470

Page 1: ...T15 Reader Installation Note T15 MIFARE Reader Black C300470 T15 MIFARE Reader White C300471 T15 Multi Tech Reader Black C300480 T15 Multi Tech Reader White C300481 T15 PIV Reader Black C305470 T15 P...

Page 2: ...eness and it should not be relied on as such To the extent permitted by law all express or implied or other representations or warranties in relation to the information are expressly excluded Neither...

Page 3: ...Copyright Gallagher Group Limited Contents 1 Introduction 4 2 Before you begin 4 3 Distance between readers 7 4 Installation 7 5 LED indications 10 6 Accessories 10 7 Technical specifications 11 8 App...

Page 4: ...ader C300470 C300471 ISO 14443A MIFARE DESFire EV1 EV2 MIFARE Plus and MIFARE Classic cards vEL7 80 HBUS only None vEL7 00 vEL1 02 T15 Multi Tech Reader C300480 C300481 ISO 14443A MIFARE DESFire EV1 E...

Page 5: ...anded security cable This cable allows the transmission of data 2 wires and power 2 wires When using a single cable to carry both power supply and data both the power supply voltage drop and data requ...

Page 6: ...devices HBUS Device Terminate HBUS Device HBUS Device HBUS Device HBUS Device HBUS Device HBUS Device Terminate Remove the on board termination jumper RS485 1 T or Star circuits are not permitted bet...

Page 7: ...WG Power 500 m 1640 ft 200 m 650 ft 450 m 1490 ft The matching of wire sizes to equivalent wire gauges are only approximate Recommended cable types for optimal HBUS RS485 performance Not applicable fo...

Page 8: ...ole this is the centre hole for which the building cable will exit the mounting surface and the two fixing holes 2 Run the building cabling out through the centre hole and through the reader bezel 3 S...

Page 9: ...BUS A Green HBUS B Brown CDXIV TX White CDXIV RX Blue HBUS Reader Note To terminate an HBUS Reader connect the Orange HBUS Termination wire to the Green HBUS A wire Cardax IV Reader connection Positiv...

Page 10: ...h the Controller but reader is not configured 1 Flash Amber Configured to a Controller but reader is not assigned to a door or elevator car On Green or Red Fully configured and functioning normally Gr...

Page 11: ...eight 139 mm 5 47 inches Width 44 mm 1 73 inches Depth 23 mm 0 9 inches Maximum number of readers on one HBUS cable 20 1 The reader is idle 2 Maximum reader current during credential read 3 The curren...

Page 12: ...ial installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communic...

Page 13: ...11 February 2022 Copyright Gallagher Group Limited 9 Mounting dimensions IMPORTANT This picture is not to scale therefore use the measurements provided 44 mm 1 73 139 mm 5 47 13 mm 1 2 diameter hole...

Reviews: