background image

2

   |  Part Number: 3E2453 R1

Installation Note  |  Gallagher T10 Mifare Reader

Before you begin

Shipment Contents

Check the shipment contains the following items:

1 x Gallagher T10 Mifare reader facia assembly

• 

1 x Gallagher T10 Mifare reader base

• 

1 x Gallagher T10 Mifare reader installation note

• 

1 x M3 Torx Post Security screw

• 

2 x self tapping pan head pozi fixing screws

• 

Power Supply

The Gallagher T10 Mifare reader receives power from the device to which 
it is connected.  The reader is designed to operate over a supply voltage 
range of 9 - 16Vdc measured at the reader terminals.  The operating 
current will be approximately 40mA (at 16Vdc) and 70mA (at 9Vdc).  
The operating current will increase to approximately 120mA (at 12Vdc) 
momentarily during a card read, beeper and LED activity.

The power source should be linear or a good quality switched-mode power 
supply.  The performance of the reader may be affected by a low quality, 
noisy power supply.

Cabling

The Gallagher T10 Mifare reader requires a minimum cable size of 4 
core 24 AWG (0.2mm

2

) stranded security cable.  This cable allows the 

transmission of data (2 wires) and power (2 wires).  When using a single 
cable to carry both power supply and data, both the power supply voltage 
drop and data requirements must be considered.  For good engineering 
design, it is recommended that the voltage at the reader should be 
approximately 12Vdc.

The critical specifications for the cable are:

Data:

The capacitance between any two wires or between  
a wire and any shielding should be less than 24nF

Power supply: The voltage at the reader must be at least 9Vdc

Examples of approved cables for connecting a single Gallagher T10 Mifare 
reader to a Controller and power supply, showing maximum cable lengths 
for each type of cable and the associated circuits are:

Summary of Contents for T10

Page 1: ...SFire EV1 Mifare Plus and Mifare Classic cards The reader sends information to the Cardax FT Controller and acts upon information sent from the Cardax FT Controller The reader itself does not make any...

Page 2: ...should be linear or a good quality switched mode power supply The performance of the reader may be affected by a low quality noisy power supply Cabling The Gallagher T10 Mifare reader requires a mini...

Page 3: ...al wall check that any reader fixed to the other side of the wall is not less than 200mm 8 inches away Wall thickness less than 200mm 200mm Installation The Gallagher T10 Mifare reader is designed to...

Page 4: ...he reader is flush with and tight against the mounting surface Note Ensure the centre hole allows the cable to run freely out through the mounting surface so that the reader facia can clip into the ba...

Page 5: ...orque of 1 5Nm 1 1 lb ft Fit screw to secure facia to base Facia Building cable Reader tail Connection Removal of the facia assembly is a simple reversal of these steps 7 Connections A Gallagher T10 M...

Page 6: ...x IV Reader 1 Connecting to the Cardax FT GBUS Universal Reader Interface Connect the wires to the sockets as shown in either of the following diagrams RLY 2 COM RLY 2 NO RLY 2 NC DATA 0 DATA 1 OUT 1...

Page 7: ...rs into the Cardax FT Command Centre system The ports to which the Gallagher T10 Mifare reader can connect are set up as groups as follows Two groups numbered 1 and 2 on the Controller 3000 4R and Fou...

Page 8: ...T 2 PB PA Positive Red Negative Black Reserved Orange Reserved Green Reserved Brown CDXIV TX White CDXIV RX Blue Cardax IV Reader Positive Red Negative Black Reserved Orange Reserved Green Reserved Br...

Page 9: ...vironmental regulations for the Restriction of Hazardous Substances in electrical and electronic equipment RoHS The RoHS directive prohibits the use of electronic equipment containing certain hazardou...

Page 10: ...is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the...

Page 11: ...Drill Template 115mm 4 53 inches 35mm 1 38 inches 44mm 1 73 inches 40mm 1 57 inches 13mm 1 2 inch diameter hole for cable 22 5mm 0 89 inches 40mm 1 57 inches...