background image

 

1-5. Maintenance, service and faults 

 

The UPS system operates with hazardous voltages. Repairs may be carried out only 
by qualified maintenance personnel.   

 

Caution - 

risk of electric shock. Even after the unit is disconnected from the mains 

(building wiring outlet), components inside the UPS system are still connected to the 
battery and electrically live and dangerous.   

 

Before carrying out any kind of service and/or maintenance, disconnect the batteries 
and verify that no current is present and no hazardous voltage exists in the terminals 
of high capability capacitor such as BUS-capacitors.   

 

Only persons are adequately familiar with batteries and with the required 
precautionary measures may replace batteries and supervise operations. 
Unauthorized persons must be kept well away from the batteries.   

 

Caution -

 risk of electric shock. The battery circuit is not isolated from the input 

voltage. Hazardous voltages may occur between the battery terminals and the ground. 
Before touching, please verify that no voltage is present!   

 

Batteries may cause electric shock and have a high short-circuit current. Please take 
the precautionary measures specified below and any other measures necessary when 
working with batteries:   

remove wristwatches, rings and other metal objects   

use only tools with insulated grips and handles.   

 

When changing batteries, install the same number and same type of batteries.   

 

Do not attempt to dispose of batteries by burning them. This could cause battery 
explosion.   

 

Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and 
eyes. It may be toxic.   

 

Please replace the fuse only with the same type and amperage in order to avoid fire 
hazards.   

 

Do not dismantle the UPS system. 

 

Summary of Contents for 1.5K

Page 1: ...Rackmount Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 1 User Manual ...

Page 2: ...nel view 3 2 2 Install the UPS 4 2 3 Setup the UPS 4 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 6 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD display wordings index 11 3 5 UPS Setting 11 3 6 Operating Mode Description 16 3 7 Faults Reference Code 16 3 8 Warning indicator 17 4 Troubleshooting 18 5 Storage and Maintenance 19 6 Specifications 20 ...

Page 3: ... over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the bu...

Page 4: ...s must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any...

Page 5: ...rd and long run models Please refer to the following model table Model No Type Model No Type 1K Standard 1KL Long run 1 5K 1 5KL 2K 2KL 3K 3KL 2 1 Rear panel view 1K 1 5K IEC 2K IEC 3K IEC 1K NEMA 1 5K NEMA 2K NEMA 3K NEMA 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Network Fax Modem surge protecti...

Page 6: ...k to the unit This UPS can be either displayed on the desk or mounted in the 19 rack chassis Please choose proper installation to position this UPS Rack mount Installation Step 1 Step 2 2 3 Setup the UPS Step 1 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords Step 2 UPS output connection For socket type outputs there two kinds of out...

Page 7: ... line cable Step 5 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 6 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during...

Page 8: ...otes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box by removing two screws on the front panel Step 4 Step 5 Step 6 Remove the top cover of battery box and replace the inside batteries After replacing the batteries put the battery box back to original l...

Page 9: ... below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells as below chart Step 4 Cover the other side of plastic shel...

Page 10: ... 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well Tapes Tapes Tapes Tapes ...

Page 11: ...m selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Setting mode Press and hold this button for 3 seconds to enter UPS setting mode when Standby an...

Page 12: ...l by 0 24 25 49 50 74 and 75 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enabled Indicates the inverter circu...

Page 13: ...igh loss LLS Low loss BAT Battery BAH Battery AH CHA Charger current CBV Charger boost voltage CFV Charger float voltage CF Converter ON ON EP EPO TP Temperature CH Charger FU Bypass frequency unstable EE EEPROM error FA Fan failure BR Battery Replacement 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and para...

Page 14: ...nverter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Output frequency setting Interface Setting Parameter 2 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency...

Page 15: ...tage Default 6V 07 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default 08 Bypass voltage range setting Interface Setting Parameter 1 2 Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Byp...

Page 16: ... low loss point from 55Hz to 59Hz Default 57 0Hz 10 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programmable outlets disable Default 11 Programmable outlets setting Interface Setting Parameter 2 Set up backup time limits for programmable outlets 0 999 setting the backup time limits in minutes from 0 99...

Page 17: ...4 2 3 4 setting the maximum charger current in 2 3 4 Ampere When the UPS is long run model the available setting options are 1 2 4 6 8 1 2 4 6 8 setting the maximum charger current in 1 2 4 6 8 Ampere Default 8A 15 Charger Boost voltage setting Interface Setting Parameter 2 Set up the charger boost voltage 225 240 setting the charger boost voltage from 225 to 240 unit 0 01V cell Default 236 16 Cha...

Page 18: ...ency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure the UPS will backup power from battery and alarm is sounding every 5 seconds Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every...

Page 19: ...nding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to remind users something wrong with battery Out of bypass voltage range Sounding every 2 seconds Bypass frequency unstable Sounding every 2 seconds EEPROM error Sounding every 2 seconds Fan failure Sounding every 2 seconds Battery replacement Sounding every 2 seconds NOTE ...

Page 20: ... flashing on LCD display and alarm is sounding every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 and the icon is lighting on LCD displa...

Page 21: ...ed Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 45 on LCD display At the same time alarm is continuously sounding The charger does not have output and battery voltage is less than 10V PC Contact your dealer 5 Storage and Maintenance 5 1 Operation...

Page 22: ...pacity Charging Current 1 5 A Max Charging Voltage 27 4 VDC 1 41 1 VDC 1 41 1 VDC 1 54 8VDC 1 82 1VDC 1 82 1VDC 1 Long run Model Type Depending on application Battery Numbers 2 3 3 4 6 6 Charging Current 1A 2A 4A 8A Charging Voltage 27 4 VDC 1 41 1 VDC 1 41 1 VDC 1 54 8VDC 1 82 1VDC 1 82 1VDC 1 ALARM Battery Mode Sounding every 5 seconds Low Battery Sounding every 2 seconds Overload Sounding every...

Reviews: