background image

1) Bypass setting 

Interface 

Description 

 

 

1. Status 

(only available in bypass / AC mode)

 

1.1 Open/Forbid: 

Open:

 Bypass allowed. When selected, UPS will run at Bypass 

mode depending on bypass enabled/disabled setting.

 

Forbid:

 Bypass not allowed. When selected, it’s not allowed for 

running in Bypass mode under any situations. 

1.2 Enable/Disable 

This option appears only when Bypass status is set to “Open”. 

Enable: 

Bypass enabled. When selected, Bypass mode is 

activated. 

Disable: 

Bypass disabled. When selected, automatic bypass is 

acceptable, but “manual bypass” is not available. “Manual bypass” 

means users manually operate UPS to Bypass mode (for example, 

in AC mode turning off the UPS to Bypass mode). Then, the UPS 

will go to bypass mode but without output if it is turned off in AC 
mode. 

 

NOTE: The following items are only available in bypass mode: 

2. HighLoss V: 

Set the acceptable high voltage for bypass. Setting 

range is from (Rated Output Volt +11V) to 276V and the default 

value is 264V.

 

3. LowLoss V:

 Set the acceptable low voltage for bypass. Setting 

range is from 110V to (Rated Output Volt - 11V) and the default 

value is 110V. 

4. HighLoss F: 

Set the acceptable high frequency for bypass. 

50 Hz: Setting range is from 51Hz to 54 Hz.   

60 Hz: Setting range is from 61Hz to 64Hz. 

The default value is 54.0Hz/64.0Hz. 

5. LowLoss F

: Set the acceptable high frequency for bypass. 

50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 

60 Hz system: Setting range is from 56.0Hz to 59.0Hz. 

The default value is 46Hz/56Hz. 

2) ECO setting 

(only available or effective on bypass mode)

 

Interface 

Description 

 

1.

 

Status 

Enable: 

Enable ECO Function

 

Disable: 

Disable ECO Function

 

If ECO function is disabled, voltage range and frequency range for 

ECO mode still can be set, but it is meaningless unless the ECO 

function is enabled.

 

2.

 

HighLoss V: 

High voltage point in ECO mode. The setting range   

is from +5% to +10% of the nominal voltage.

 

3.

 

LowLoss V: 

Low voltage point in ECO mode. The setting range is   

from -5% to -10% of the nominal voltage.

 

4.

 

HighLoss F: 

Set low frequency point for ECO mode.

 

50 Hz system: Setting range is from 46Hz to 48Hz.

 

60 Hz system: Setting range is from 56Hz to 58Hz.

 

The default value is 48Hz/58Hz. 

5.

 

LowLoss F:

 Set high frequency point for ECO mode.   

50 Hz: Setting range is from 52.0Hz to 54.0 Hz.   

60 Hz: Setting range is from 62.0Hz to 64.0Hz. 

The default value is 52.0Hz/62.0Hz. 

 

Summary of Contents for 6KRT

Page 1: ...6K 10K Rack Tower Online UPS Uninterruptible Power Supply System Version 1 2 User Manual...

Page 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Page 3: ...er Installation 9 2 4 Single UPS Installation 10 2 5 Parallel UPS Installation 11 3 Operations 12 3 1 Operating Mode Status Description 12 3 2 Button Operation 12 3 3 LED Indicators 13 3 4 Audible ala...

Page 4: ...llation Do not connect appliances or devices which would overload the UPS e g big motor type equipment Place cables in such a way that no one can step on or trip over them Do not block air vents in th...

Page 5: ...of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presence of a flammable anesthetic mixture with air oxygen or n...

Page 6: ...PS system The UPS can be operated by any individuals with no previous experience 1 6 Standards Safety IEC EN 62040 1 EMI Conducted Emission IEC EN 62040 2 Category C3 Radiated Emission IEC EN 62040 2...

Page 7: ...cable option One USB cable One parallel cable and one share current cable option One battery cable option Two sets of tower stands including feet and extensions Mounting ears NOTE Before installation...

Page 8: ...4 Share current port for parallel function 5 Parallel port for parallel function 6 Intelligent slot 7 EMBS External Maintain Bypass Switch port 8 Cooling fan 9 External battery connector 10 Input circ...

Page 9: ...3U Assemble two feet and one short extension as one tower stand shown in step 1 Align the two stands approximately 35cm apart in step 2 Then put UPS module in the stands as shown in step 3 Step 1 Step...

Page 10: ...gh for the rated capacity of UPS to avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s ma...

Page 11: ...nection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correct Pay highly attention to the polarity marking on external battery connector...

Page 12: ...frequency 50 Hz or 60 Hz through the inverter The UPS will still charge battery at this mode There is no bypass at this mode Battery Mode When the input voltage is out of the acceptable range or powe...

Page 13: ...ON position then the fan will be running and the UPS supplies power to the loads via bypass The UPS is operating in Bypass mode NOTE When UPS is in Bypass mode the output voltage comes directly from...

Page 14: ...inter the in rush current should be calculated carefully to see if capacity of the UPS can cover due to the huge starting power consumption of this kind of load 3 If the UPS is overload the buzzer wil...

Page 15: ...urn off the UPS with utility power supply in Line mode 1 When LCD is on home page press the OFF ESC button LCD will show a prompt page of Turn Off Move the arrow to Yes by up or down button then press...

Page 16: ...and the jumpers on the control board should be re set as below table Note 1 insert with jumper 0 no jumper x these pins are for other functions NOTE This operation should be done by professional tech...

Page 17: ...UPS Info Page 6 Others Fault Info Warning Info Bypass ECO Output Battery Calibration Others Press button Enter Press button Enter Press button Enter Press button Enter Press button Enter Press button...

Page 18: ...splay five items in operation menu Control Measurement Information Setting Alarm 2 Press UP or DOWN button to select item 3 Press ON ENTER button to confirm the selection 4 Press OFF ESC button to ret...

Page 19: ...rk well in battery mode and test the battery performance This selection will be displayed under all UPS modes However it couldn t execute this test in Battery Fault Eco mode and reminder will pop up i...

Page 20: ...e Before restart the parallel system please confirm this selection first NOTE Before executing this action you must check if the system cables and connections are connected correctly and safely Please...

Page 21: ...his menu is used to configure the parameter settings or do the calibrations NOTE Some settings will be only available in some operation modes If the setting is not available in current mode the LCD wi...

Page 22: ...Volt 11V and the default value is 110V 4 HighLoss F Set the acceptable high frequency for bypass 50 Hz Setting range is from 51Hz to 54 Hz 60 Hz Setting range is from 61Hz to 64Hz The default value is...

Page 23: ...requency within 46 54 Hz for 50Hz system or within 56 64 Hz for 60Hz system NOTE CVCF means Constant Voltage and Constant Frequency it represents converter mode 4 Battery setting available on all oper...

Page 24: ...s line ECO converter mode NOTE Before making charger output voltage adjustment be sure to disconnect all batteries first to get the accurate charger voltage Be careful that the adjustment should be su...

Page 25: ...AH 12AH 17AH 26AH 40AH 65AH 100AH and so on The default value is 9AH Factor Calibrate the displayed backup time by adjusting this multiplier factor The formulation is listed below Displayed backup tim...

Page 26: ...3 7 2 6 Alarm page This page records and displays the faults or warning events happened in history...

Page 27: ...to the table below Alarm type LCD display Possible cause Remedy Warning 01 Batt Open 1 The battery is not connected well 2 The battery protection device is open 1 Connect the battery well 2 Replace or...

Page 28: ...parallel system is fault because of parallel communication failure When this warning appeared the UPS could not start up because it is system protection for parallel system 1 If the system is still n...

Page 29: ...and short Contact the dealer to repair Fault 24 Inv Rly Short The internal inverter relay is stick to short or the SCR of STS Static Transfer Switch is short Contact the dealer to repair Fault 35 Para...

Page 30: ...equired precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and th...

Page 31: ...to 90 capacity 9 hours recover to 90 capacity Charging Current 1 A 10 max Charging Voltage 273 V 1 Long Run Model Type Depending on applications Numbers 18 20 Charging Current 4 A 10 max Charging Volt...

Reviews: