Fault 

04: Bus Unbalance 

1)

 

The load is special or abnormal, 

so  the  internal  positive  and 

negative  DC  bus  voltages  are 

unbalanced. 

2)

 

The internal converter failed. 

Contact the dealer. 

Fault 

11: Inv Start Fail 

The  internal  inverter  failed,  so  the 

inverter  voltage could not  start  up       

correctly. 

Contact the dealer to repair. 

Fault 

12: Inv Volt High 

The  internal  inverter  failed,  so  the 

inverter voltage is too high. 

Contact the dealer to repair. 

Fault 

13: Inv Volt Low 

The  internal  inverter  failed,  so  the 

inverter voltage is too low. 

Contact the dealer to repair. 

Fault 

14: Output Short 

Short  circuit  occurs  on  the  UPS 

output. 

Remove short circuit. 

Fault 

1A: NegPower   

UPS  output  power  is  negative.  It 

means  there  is  energy  feedback 

into  the  internal  of  UPS  from 

output.  It  may  be  caused  by 

regenerative load or current control 

failure in the parallel system. 

Contact the dealer. 

Fault 

21: Batt SCR Short    The  internal  battery  SCR  is  failed 

and short. 

Contact the dealer to repair. 

Fault 

24: Inv Rly Short 

The internal inverter relay is stick to 

short  or  the  SCR  of  STS  (Static 

Transfer Switch) is short. 

Contact the dealer to repair. 

Fault 

35: Para Comm Fail 

Parallel cable for communication is 

not  connected  well  in  the  parallel 

system. 

Connect the parallel cable well. 

Fault 

36: OP.I Unbalance 

The  output  current  is  extremely 

unbalanced between the paralleled 

UPSs  or  there  is  an  error  in  the 

parallel system. 

Contact the dealer to repair. 

Fault 

41: Over Temp 

The  internal  temperature  is  too 

high  and  reach  the  fault  level 

(shutdown): 

1)

 

Maybe the environment is hot. 

2)

 

Maybe  the  fan  is  blocked  or 

failed. 

3)

 

Maybe ventilation is blocked by 

the wall or other goods. 

4)

 

Load is too heavy. 

1)

 

Make  sure  the  ambient 
temperature not over 40

º

C. 

2)

 

Make sure the fan is OK. 

3)

 

Make sure ventilation is well. 

4)

 

Remove  some  loads  if 

possible. 

Fault 

42: CPU Comm Fail 

Internal  communication  failure 

between CPUs. 

Contact the dealer to repair. 

Fault 

43: Over load  

Overload  time  is  out  of  the 

specification  and  the  UPS  shuts 
down automatically. 

Remove excess loads from UPS 

output and restart it. 

 

Summary of Contents for 6KRT

Page 1: ...6K 10K Rack Tower Online UPS Uninterruptible Power Supply System Version 1 2 User Manual...

Page 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Page 3: ...er Installation 9 2 4 Single UPS Installation 10 2 5 Parallel UPS Installation 11 3 Operations 12 3 1 Operating Mode Status Description 12 3 2 Button Operation 12 3 3 LED Indicators 13 3 4 Audible ala...

Page 4: ...llation Do not connect appliances or devices which would overload the UPS e g big motor type equipment Place cables in such a way that no one can step on or trip over them Do not block air vents in th...

Page 5: ...of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presence of a flammable anesthetic mixture with air oxygen or n...

Page 6: ...PS system The UPS can be operated by any individuals with no previous experience 1 6 Standards Safety IEC EN 62040 1 EMI Conducted Emission IEC EN 62040 2 Category C3 Radiated Emission IEC EN 62040 2...

Page 7: ...cable option One USB cable One parallel cable and one share current cable option One battery cable option Two sets of tower stands including feet and extensions Mounting ears NOTE Before installation...

Page 8: ...4 Share current port for parallel function 5 Parallel port for parallel function 6 Intelligent slot 7 EMBS External Maintain Bypass Switch port 8 Cooling fan 9 External battery connector 10 Input circ...

Page 9: ...3U Assemble two feet and one short extension as one tower stand shown in step 1 Align the two stands approximately 35cm apart in step 2 Then put UPS module in the stands as shown in step 3 Step 1 Step...

Page 10: ...gh for the rated capacity of UPS to avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s ma...

Page 11: ...nection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correct Pay highly attention to the polarity marking on external battery connector...

Page 12: ...frequency 50 Hz or 60 Hz through the inverter The UPS will still charge battery at this mode There is no bypass at this mode Battery Mode When the input voltage is out of the acceptable range or powe...

Page 13: ...ON position then the fan will be running and the UPS supplies power to the loads via bypass The UPS is operating in Bypass mode NOTE When UPS is in Bypass mode the output voltage comes directly from...

Page 14: ...inter the in rush current should be calculated carefully to see if capacity of the UPS can cover due to the huge starting power consumption of this kind of load 3 If the UPS is overload the buzzer wil...

Page 15: ...urn off the UPS with utility power supply in Line mode 1 When LCD is on home page press the OFF ESC button LCD will show a prompt page of Turn Off Move the arrow to Yes by up or down button then press...

Page 16: ...and the jumpers on the control board should be re set as below table Note 1 insert with jumper 0 no jumper x these pins are for other functions NOTE This operation should be done by professional tech...

Page 17: ...UPS Info Page 6 Others Fault Info Warning Info Bypass ECO Output Battery Calibration Others Press button Enter Press button Enter Press button Enter Press button Enter Press button Enter Press button...

Page 18: ...splay five items in operation menu Control Measurement Information Setting Alarm 2 Press UP or DOWN button to select item 3 Press ON ENTER button to confirm the selection 4 Press OFF ESC button to ret...

Page 19: ...rk well in battery mode and test the battery performance This selection will be displayed under all UPS modes However it couldn t execute this test in Battery Fault Eco mode and reminder will pop up i...

Page 20: ...e Before restart the parallel system please confirm this selection first NOTE Before executing this action you must check if the system cables and connections are connected correctly and safely Please...

Page 21: ...his menu is used to configure the parameter settings or do the calibrations NOTE Some settings will be only available in some operation modes If the setting is not available in current mode the LCD wi...

Page 22: ...Volt 11V and the default value is 110V 4 HighLoss F Set the acceptable high frequency for bypass 50 Hz Setting range is from 51Hz to 54 Hz 60 Hz Setting range is from 61Hz to 64Hz The default value is...

Page 23: ...requency within 46 54 Hz for 50Hz system or within 56 64 Hz for 60Hz system NOTE CVCF means Constant Voltage and Constant Frequency it represents converter mode 4 Battery setting available on all oper...

Page 24: ...s line ECO converter mode NOTE Before making charger output voltage adjustment be sure to disconnect all batteries first to get the accurate charger voltage Be careful that the adjustment should be su...

Page 25: ...AH 12AH 17AH 26AH 40AH 65AH 100AH and so on The default value is 9AH Factor Calibrate the displayed backup time by adjusting this multiplier factor The formulation is listed below Displayed backup tim...

Page 26: ...3 7 2 6 Alarm page This page records and displays the faults or warning events happened in history...

Page 27: ...to the table below Alarm type LCD display Possible cause Remedy Warning 01 Batt Open 1 The battery is not connected well 2 The battery protection device is open 1 Connect the battery well 2 Replace or...

Page 28: ...parallel system is fault because of parallel communication failure When this warning appeared the UPS could not start up because it is system protection for parallel system 1 If the system is still n...

Page 29: ...and short Contact the dealer to repair Fault 24 Inv Rly Short The internal inverter relay is stick to short or the SCR of STS Static Transfer Switch is short Contact the dealer to repair Fault 35 Para...

Page 30: ...equired precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and th...

Page 31: ...to 90 capacity 9 hours recover to 90 capacity Charging Current 1 A 10 max Charging Voltage 273 V 1 Long Run Model Type Depending on applications Numbers 18 20 Charging Current 4 A 10 max Charging Volt...

Reviews: