Required conditions for time band management:
- clock board present;
- selected "via bands" set-point automatic variation (
User menu
Set-points and
parameters
H4
).
Secondary set-point from a digital input
(
Set-point menu
F3
)
The summer and winter secondary set-point values, controlled from the digital input
ID14, accessible from terminals X3:61-62, can be set from the SET-POINT menu. The
regulation will use the main set-point when the digital input is open and the secondary
set-point when it is closed.
Condition:
- digital input configured as “ -> secondary set-point” (
User menu
Set-points and
parameters
H1
);
- selected "via digital input" set-point automatic variation (
User menu
Set-points
and parameters
H4
).
DIN14 CONFIGURATION
H1
-› SECONDARY SET-POINT
SET-POINT
H4
AUTOMATIC VARIATION
-› VIA A DIGITAL INPUT
6.3.5
ALARMS
In the event of an anomaly or the unit is blocked due to a safety device being triggered, the red LED beneath the ALARM key
lights up.
Press the ALARM key once to access the list of active alarms, then use the UP and DOWN keys to scroll the list. Each alarm is
identified by a code and a brief description; the complete list is found in the software manual.
Press the ALARM key again to reset the alarms, provided the cause that triggered them has been resolved.
If the specific function is enabled, all the alarms besides the high and low pressure alarms are automatically reset after a pre-
set time interval.
Information that at least one alarm is active can be communicated externally via a potential-free contact in wired exchange
on terminals X3:31-32-33 (see Wiring diagram), or if a supervision systems is available, the status of each alarm can be read
together with that of the main alarm, the alarms can be reset and a datalogger can be set up (pCOWeb).
The information regarding triggered alarms on terminals 31-32-33 can be used to:
- remote control the alert (e.g. via a warning light);
- activate an auxiliary backup device for DHW production (e.g. an electric resistance in the tank controlled by a mechanical
thermostat).
SET-POINT
H4
AUTOMATIC VARIATION
-› VIA TIME BANDS
SETTING THE
F3
SECONDARY SET-POINT
COOLING
: 00.0˚C
HEATING
: 00.0˚C