LCX
RG66010687_rev.00
46
Cooling mode: outdoor air temperature 35°C, water temperature 12°C / 7°C (EN 14511)
Heating mode: outdoor air temperature 7°C dry bulb and 6.2°C wet bulb, water temperature 40°C/45°C (EN 14511)
Sound power measured according to standards ISO 3741 - ISO 3744 and EN 29614-1
Sound pressure measured at a distance of 10 m and a height of 1.5 m above the ground in a clear field.
Approx. capacity (kW)
45
50
60
70
80
Efficiency Pack
2
2
2
2
2
1
2
4
1
2
4
1
2
4
LCX…HS
042
052
062
072
082
091
092
094
101
102
104
121
122
124
Power supply
V-ph-Hz
Cooling capacity (UNI14511)
kW
-
-
57,4
65,6
77,1
87,4
87,4
-
100,1
100,1
-
111,2
111,2
117,3
Total power input in cooling mode (UNI14511)
kW
-
-
20,9
23,6
27,1
32,1
32,1
-
36,4
36,4
-
40,4
40,4
42,0
Rated current input
A
-
-
36
40
46
55
55
-
62
62
-
69
69
72
EER (UNI14511)
-
-
2,74
2,78
2,85
2,72
2,72
-
2,75
2,75
-
2,75
2,75
2,80
ESEER
-
-
3,60
3,64
3,72
3,23
3,54
-
3,65
3,30
-
3,29
3,61
3,69
Eurovent Efficency Class
-
-
C
C
C
C
C
-
C
C
-
C
C
C
Heating capacity
kW
-
-
69,5
79,2
93,5
105
107
-
120
120
-
134
134
147
Total power input in heating mode
kW
-
-
19,8
22,1
25,7
30,0
30,0
-
34,2
34,2
-
38,1
38,1
41,7
Rated current input
A
-
-
34
37
43
51
51
-
58
58
-
65
65
71
COP (UNI14511)
-
-
3,51
3,58
3,64
3,51
3,55
-
3,52
3,52
-
3,52
3,50
3,52
Maximum current input
A
-
-
60
64
75
91
91
-
101
101
-
119
119
120
Starting current
A
-
-
195
192
200
261
261
-
269
269
-
319
319
247
Starting current with Soft-Starter kit
A
-
-
120
133
148
199
199
-
207
207
-
254
254
172
No. of scroll compressors / circuits
-
-
2 / 1
2 / 1
2 / 1
2 / 2
2 / 1
-
2 / 2
2 / 1
-
2 / 2
2 / 1
4 / 2
No. of axial fans
-
-
4
4
4
6
6
-
6
6
-
8
8
8
Air flow rate
m
3
/h
-
-
21379
21379
21379
30913
30913
-
30913
30913
-
41340
41340
41340
Water flow rate (cooling)
l/h
-
-
9895
11303
13293
15063
15062
-
17262
17263
-
19162
19159
20214
Pressure drop, water side (cooling)
kPa
-
-
23
23
23
24
24
-
26
26
-
27
27
25
Available head, standard pump (cooling)
kPa
-
-
148
145
142
138
138
-
133
133
-
122
122
124
Buffer tank
dm
3
-
-
200
200
200
220
220
-
220
220
-
340
340
340
Expansion tank
dm
3
-
-
12
12
12
12
12
-
12
12
-
12
12
12
Plumbing connections
"
-
-
2
2
2
2
2
-
2
2
-
2
1
/
2
2
1
/
2
2
1
/
2
Height
mm
-
-
1735
1735
1735
1735
1735
-
1735
1735
-
1735
1735
1679
Length
mm
-
-
2090
2090
2090
2442
2442
-
2442
2442
-
3190
3190
3540
Depth
mm
-
-
1183
1183
1183
1183
1183
-
1183
1183
-
1183
1183
1183
Sound power level
dB(A)
-
-
82
82
82
83
83
-
83
83
-
83
83
82
Sound pressure level
dB(A)
-
-
54
54
54
55
55
-
55
55
-
55
55
54
Base unit operating weight
kg
-
-
540
570
650
730
730
-
730
730
-
1010
1010
1050
Unit with pump and full tank operating weight
kg
-
-
877
907
987
1138
1138
-
1138
1138
-
1581
1581
1641
400-3N-50
Rated technical data of LCX…H heat pumps, STANDARD version
90
100
120