Service and installation manual - C.H. Water Boiler
© All rights reserved - Galmet Sp. z o.o. Sp. K.
12
4.4. Connecting of boiler to chimney and installation
The boiler should be connected directly to the chimney or via a connection made from steel sheet with diameter enabling its tight positioning. The
connection should have a cleaning hole and should slightly rise up. The chimney should be made in compliance with PN-91/B-02413 standard. Relevant
height and cut section of the chimney duct have significant influence on correct boiler operation. Technical condition of the chimney, to which the boiler is
to be connected should be assessed by a chimney firm. In case when there is a problem with the chimney draught, which is transferred to incorrect boiler
operation, a chimney cowl or a draught generator or an exhaust fan may be used. The above devices aid and stabilize chimney draught.
1
4
3
5
2
Drawing 8 - Connecting boiler to chimney
1. Boiler 2. Flue 3. Chimney duct 4. Chimney connection 5. Chimney cleaning hole
Connect the boiler to the installation in a separable way!
Connection of the boiler to the central heating, electric, water main and chimney installations acc. to regulations in force and instruction manual is performed
by an installer. He also performs the first lighting up of the boiler and confirms it with an entry in the guarantee card.
5. Operation and service
Prior to commencing lighting up the fixed retort combustion box should be sealed.
5.1. Lighting up
Lighting up is performed acc. to commands displayed on the screen of eLider controller and the fuel bin is filled up with dry eco-pea coal SILESIAN.
5.2. Air adjustment
Combustion process is controlled by the boiler controller, which controls operation of the feeder and fan on the basis of the set temperature and constant
temperature measurements. In order the fuel that is fed on the combustion box pan is burned completely relevant volume of air should be selected. It is the
parameter, which should be adjusted individually for each kind of fuel and draught in chimney. After correct setting of this parameter, the boiler operates
automatically and its operation depends on resupplying the fuel, removing ash and periodical cleaning. The fuel should burn on a mound above the edge of
the burner ring. The flame of burning fuel should be bright, steady with no flickering ends.
4. Assembly / 5. Operation and service