background image

Specialised commercial taps and valves

© Galvin Engineering Pty Ltd: 2011

CliniLever

® 

Healthcare Tapware

1.  From fixing kit fit 'O'ring (10) into groove in the 

underside of mixer body (9), screw studs (11) into 
underside of mixer body (9).

2.  Apply suitable lubricant to 'O'rings (12). Pass flexible 

tail (16) (with red indication) up through deck hole 
and install into hole marked 'H' in underside of 
mixer body (9). Pass remaining flexible tail (with blue 
indication) up through deck hole and install into hole 
marked 'C'. Tighten both tails (16) firmly by hand.

3.  Place mixer over vanity cut out, fit gasket (13) and 

fixing plate (14) over studs (11) then screw on fixing 
nuts (15). Position mixer as required then tighten 
fixing nuts (15).

4.  Connect the flexible tails (16) to the hot and cold 

isolating stop taps, taking care that flexible tails 
are not kinked, twisted or in tension as they are 
tightened

Important

Replacing Cartridge

TM-BASCP

Important Information

Installation 

(Fig 1)

CliniLever

® 

Single Lever Basin Mixer

-  All pipework must be thoroughly flushed prior to 

installation as foreign materials may block the flow 
regulating device and reduce the flow of water. 
Note: Aerator insert housing must be retightened 
to prevent removal by hand. 

-  Not suitable for gravity feed systems.

-  Mixer is fitted with a 5 L/min flow regulated 

aerator insert. This low flow rate may not be 
suitable for connection to some Instantaneous 
Gas Water Heaters, some Tempering Valves, 
some Solar Water Heaters and some 
Thermostatic Mixing Valves.

-  Check with the manufacturers of these products.

-  Isolating stop taps are recommended to be fitted 

to the inlet connections.

Pressure & Temperature Requirements.

-  Hot and cold water inlet pressures should be equal.

-  Inlet pressure range: 150-500 kPa 
 

(Ref. AS/NZS 3500.1 -2003, Clause 3.3.4)

-  Maximum hot water temperature : 80

°C.

Deck Requirements

-  Deck thickness: 45mm maximum

-  Tap body hole (in deck): Ø33-35mm

1.  Turn off hot and cold water supplies at isolating stop 

taps.

2.  Remove indicator plug (3). Using 2.5mm allen key 

(4) loosen screw (2) and remove handle (1). Remove 
cap (5) taking care not to damage the decorative 
finish. Unscrew nut (6) then lift out old cartridge (8).

3.  Ensure inside face of mixer body (9) is clean. Fit new 

cartridge (8) into mixer body, taking care that two 
lugs on base of cartridge (8) fit into mating holes in 
mixer body (9).

4.  Screw on nut (6). Important: Nut (6) should be 

tightened to a torque of 12 Nm.

5.  Replace cap (5), tightening by hand. Fit handle 

(1) taking care that it is pushed fully down, tighten 
screw (2) and replace indicator plug  (3), position 
with red to the left.

6.  Turn on isolating stop taps and check operation.
7.  To adjust the maximum hot water temperature refer 

to the instruction on the next page:-  'Adjusting the 
anti-scald stop ring'.

July 2015

Reviews: