Specialised commercial taps and valves
© Galvin Engineering Pty Ltd: 2011
CliniLever
®
Healthcare Tapware
1. From fixing kit fit 'O'ring (10) into groove in the
underside of mixer body (9), screw studs (11) into
underside of mixer body (9).
2. Apply suitable lubricant to 'O'rings (12). Pass flexible
tail (16) (with red indication) up through deck hole
and install into hole marked 'H' in underside of
mixer body (9). Pass remaining flexible tail (with blue
indication) up through deck hole and install into hole
marked 'C'. Tighten both tails (16) firmly by hand.
3. Place mixer over vanity cut out, fit gasket (13) and
fixing plate (14) over studs (11) then screw on fixing
nuts (15). Position mixer as required then tighten
fixing nuts (15).
4. Connect the flexible tails (16) to the hot and cold
isolating stop taps, taking care that flexible tails
are not kinked, twisted or in tension as they are
tightened
Important
Replacing Cartridge
TM-BASCP
Important Information
Installation
(Fig 1)
CliniLever
®
Single Lever Basin Mixer
- All pipework must be thoroughly flushed prior to
installation as foreign materials may block the flow
regulating device and reduce the flow of water.
Note: Aerator insert housing must be retightened
to prevent removal by hand.
- Not suitable for gravity feed systems.
- Mixer is fitted with a 5 L/min flow regulated
aerator insert. This low flow rate may not be
suitable for connection to some Instantaneous
Gas Water Heaters, some Tempering Valves,
some Solar Water Heaters and some
Thermostatic Mixing Valves.
- Check with the manufacturers of these products.
- Isolating stop taps are recommended to be fitted
to the inlet connections.
Pressure & Temperature Requirements.
- Hot and cold water inlet pressures should be equal.
- Inlet pressure range: 150-500 kPa
(Ref. AS/NZS 3500.1 -2003, Clause 3.3.4)
- Maximum hot water temperature : 80
°C.
Deck Requirements
- Deck thickness: 45mm maximum
- Tap body hole (in deck): Ø33-35mm
1. Turn off hot and cold water supplies at isolating stop
taps.
2. Remove indicator plug (3). Using 2.5mm allen key
(4) loosen screw (2) and remove handle (1). Remove
cap (5) taking care not to damage the decorative
finish. Unscrew nut (6) then lift out old cartridge (8).
3. Ensure inside face of mixer body (9) is clean. Fit new
cartridge (8) into mixer body, taking care that two
lugs on base of cartridge (8) fit into mating holes in
mixer body (9).
4. Screw on nut (6). Important: Nut (6) should be
tightened to a torque of 12 Nm.
5. Replace cap (5), tightening by hand. Fit handle
(1) taking care that it is pushed fully down, tighten
screw (2) and replace indicator plug (3), position
with red to the left.
6. Turn on isolating stop taps and check operation.
7. To adjust the maximum hot water temperature refer
to the instruction on the next page:- 'Adjusting the
anti-scald stop ring'.
July 2015