UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0
25
Figure 7: Dimensions of the Gamatronic UPS
Table 1: Recommended clearances
R
ECOMMENDED MINIMUM CLEARANCE AROUND THE
UPS
Front
110 cm (43 in.) Minimum adequate clearance for user access and service.
Rear
100 cm (39 in.) Minimum adequate clearance for cable connections.
Sides
--
No minimum clearance, provided that the UPS is not placed next
to heat-emitting or electronic equipment. If the UPS is placed
next to heat-emitting or electronic equipment, leave at least
20 cm free space between the UPS and the other equipment. The
object here is to avoid subjecting the UPS to additional heat and
to protect the UPS from stray electronic signals.