UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0
39
6.
If you are using lithium-ion batteries, contact Gamatronic support for configuration
instructions.
Figure 20: Connecting a Single Battery Set
UPS KVA
20
40
60
UPS KW
18
36
54
DC CURRENT
53
106
159
Table 3: Battery current ratings for semiconductor fuses and circuit breakers
7.
The fuses between the battery cabinets and The UPS (F1, F2, F3, and F4 in Figure 20)
must be
FAST FUSES (SEMICONDUCTOR FUSES)
; for example, the Ferraz Shawmut
A70QS fuse.
8.
For initial startup to take place the battery must be connected to the UPS and available.
Current values are for fuses F1 through F4 in Figure 20 and are based on 10-
minute backup time at full load. If longer backup time is required, please consult
with Gamatronic Support.