UPS for 208 Vac Grid, B60US-IB Installation Guide, doc. rel. 3.0
83
Figure 66: The crown icon indicates the Master UPS
A crown shaped icon appears on the Master Power Module. From the System
Menu go to
Status > Modules
to view it.
Only one power module within the set of power modules is designated Master
Power Module.
Figure 67: Modules screen
9.
Put the slave systems in multisystem mode.
(
System Menu > Setup > System Type > Multisystem mode
)
10.
For each slave system, compare the output voltage of each phase to that of the Master
system.
Any voltage difference should be no greater than 2 %.
If the difference in output voltage is greater than 2 % for any phase, navigate to the
System
Menu > Status
screen, tap the
Modules
icon, and then tap the
Output
tab at the bottom of
the page.
The following screen appears:
Summary of Contents for B60US-IB
Page 4: ......