56
required, and indicate how many of the modules are intended to provide redundancy. The
Centric User Guide
provides more information on redundancy.
A password is required to perform this function. If you do not have the required password,
contact your distributor or sales agent.
Figure 57: “Number of modules” screen
4.
From the system main menu, choose "Operation > Turn on/off > Modules off".
5.
On the screen, choose the module to be removed. The modules are numbered from bottom
to top. The outline of the module you choose becomes highlighted.
Figure 58: Turning off a module
6.
Press the "Complete Shutdown" button.
7.
To verify that the module has been shut down, navigate to the module status screen
("Main screen > Status > Modules"), press on the icon of the module you just shut down,
and verify that the status is "OFF" for these five items: PFC, Inverter, Dc relay, Input relay,