Centric Installation Guide, rel. 4.7
33
3.3.1 Continuing first-time start-up process
1.
Verify again
that the batteries have been connected to the Centric with proper polarity.
2.
If you are using lithium-ion batteries, check the values in
the “Setup > Battery” parameters
against the information in the battery manufacturer’s data sheet. Verify that the parameter
values are appropriate for the batteries you have chosen.
3.
Switch ON the battery cabinet circuit breaker, and/or close the fuse holders between the
battery cabinet(s).
4.
On the
Centric
main menu, choose "Operation > Turn on/off > System on".
5.
Return to the main menu by tapping on the "home" icon in the upper left corner of the
Centric
screen.
6.
On the main menu screen, if the alarm symbol (a yellow triangle) is displayed, press the
alarm symbol to display the potential problems. Refer to the troubleshooting section of this
document to determine the proper response to the alarm indications.
Figure 19: The "alarms" icon indicates alarm conditions
7.
Perform a 5 minute battery test to verify that the
Centric
is ready and able to operate in
battery mode when needed. Verify that the ac output circuit breakers on the electrical board
are OFF. To perform a battery test, from the main menu choose:
"Operation > Battery test > Test battery", verify the duration is set to 5 minutes.
8.
You can now connect a load device to the ac output, and then turn ON the ac output circuit
breakers on the electrical board.
9.
Now you must update the last maintenance date. From the main menu, choose
"Setup > Time > Set last maintenance date". Tap on the line that says "Last maintenance
date". Press "confirm", and enter the system password if prompted for it.
10. Finally, to save the settings you have defined, from the main menu choose:
"Setup > Save and restore > Save settings > OK".