CENTRIC 3x480, User Guide, rel. 1.7
Register
Variable name
GET Values
Remarks
22 4x0022 Input Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
24 4x0024 Output Source
0: Normal
1: On Battery
2: On Bypass
3: Reducing
4: Boosting
5: Other
6: None
Depends on the UPS topology
25 4x0025 Output Frequency
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
26 4x0026 Output Number Of Lines
1 to 3
Number of the UPS output phases
27 4x0027 Output Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
28 4x0028 Output Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
30 4x0030 Output Load Line 1
%
Some units might show values over 100% in case of overload
31 4x0031 Output Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
32 4x0032 Output Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
34 4x0034 Output Load Line 2
%
Some units might show values over 100% in case of overload
35 4x0035 Output Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
36 4x0036 Output Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
38 4x0038 Output Load Line 3
%
Some units might show values over 100% in case of overload
39 4x0039 Bypass Frequency
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
40 4x0040 Bypass Number Of Lines
1 to 3
Number of the UPS bypass phases
41 4x0041 Bypass Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
42 4x0042 Bypass Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
44 4x0044 Bypass Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
45 4x0045 Bypass Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
47 4x0047 Bypass Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
48 4x0048 Bypass Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
50 4x0050 Temperature Alarm
0: Alarm off
1: Alarm on