CENTRIC 3x480, User Guide, rel. 1.7
Register
Variable name
GET Values
Remarks
210 4x0210 Seconds On Battery
Seconds
Only available during power failure, otherwise zero
211 4x0211 Estimated Backup Time
Minutes
Only available during power failure and when the battery is fully charged (6 in 4x0209),
otherwise zero. This value is a rough approximation received by mathematical
calculations, and assumes new and healthy batteries of average VRLA type in initial fully
charged state.
212 4x0212 Estimated Charge
0-100%
Mathematical calculation of battery charge in percents; will send 200 if no value has been
calculated
213 4x0213 DC Voltage positive
×10 Vdc
Divide the value by 10 for real measurement: 4051/10=405.1 Vdc
214 4x0214 DC Voltage Negative
×10 Vdc
Divide the value by 10 for real measurement: 4051/10=405.1 Vdc
215 4x0215 DC Voltage total
×10 Vdc
Divide the value by 10 for real measurement: 8102/10=810.2 Vdc
216 4x0216 Battery Current
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
217 4x0217 Battery Temperature
°C
Degrees centigrade
218 4x0218 Number of phases
1 to 3
Number of the UPS phases (always 3 for current units)
219 4x0219 Inverter Frequency Line 1
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
220 4x0220 Inverter Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
221 4x0221 Inverter Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
222 4x0222 Inverter Power Line 1
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
223 4x0223 Inverter Apparent Power Line 1
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
224 4x0224 Inverter Frequency Line 2
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
225 4x0225 Inverter Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
226 4x0226 Inverter Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
227 4x0227 Inverter Power Line 2
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
228 4x0228 Inverter Apparent Power Line 2
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
229 4x0229 Inverter Frequency Line 3
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
230 4x0230 Inverter Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
231 4x0231 Inverter Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
232 4x0232 Inverter Power Line 3
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
233 4x0233 Inverter Apparent Power Line 3
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
234 4x0234 Charger Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac