CENTRIC 3x480, User Guide, rel. 1.7
5.2.2
Operation
The Operation option on the Main Menu is used to turn the UPS on or off.
(For a full description of all of the Operation menu functions, see section
7.3.)
5.2.2.1
TURNING THE UPS ON (FOLLOWING NORMAL SHUTDOWN)
To turn the UPS on:
1.
Verify that the battery circuit breaker is in the OFF position.
(The battery circuit breaker is not located on the UPS. It is either on the battery box or on the cables
between the battery box and the UPS.)
2.
On the Main Menu, tap the
Operation
button. The Operation submenu appears.
Figure 8: The Operation submenu
3.
Tap the top button labeled "
Turn on / off
" on the Operation submenu.
Another menu appears (Figure 9).
4.
Tap the "System on" button.
Figure 9: The "Turn off / on" submenu