G
AMATRONIC
E
LECTRONIC
I
NDUSTRIES
L
TD
.
CENTRIC 3x480, User Guide, rel. 1.7
75
7.2.11
Setup > SAVE & RESTORE
This set of functions let you save the current UPS settings, and restore them later. This would enable you
to experiment with new settings and then easily return to the previous settings. There is also an option to
restore the factory default settings.
Figure 56: "Setup > Save & Restore" options
7.2.11.1
SETUP > SAVE & RESTORE > SAVE SETTINGS
Saves the current settings of the UPS in non-volatile memory.
7.2.11.2
SETUP > SAVE & RESTORE > RESTORE SETTINGS
Restores to active status the settings that you previously saved in non-volatile memory.
7.2.11.3
SETUP > SAVE & RESTORE >RESTORE FACTORY SETTINGS
This function is displayed only in “Technician” mode. Restores to active status the "factory default" settings
of the UPS. Performing this function does not have any effect on what is saved by the SAVE SETTINGS
function above.
Be aware that using the "restore factory settings" returns the
Centric
settings to what they were when the
unit arrived at your premises. If, for example, you have since added additional power modules, the settings
will not include the additional modules and you must readjust the settings to include the additional modules.