Gamatronic Electronic Industries Ltd.
70
CENTRIC User Guide, Release 0.3
L
INE
#
A
LARM MESSAGE
E
XPLANATION
,
RECOMMENDED ACTION
(
IF ANY
)
D
EFAULT
S
EVERITY
25
Battery test in progress.
A battery test is in progress.
Information
26
Auxiliary #1 fault.
Input dry contact #1 has been activated.
Warning
27
Auxiliary #2fault.
Input dry contact #2 has been activated.
Warning
28
Auxiliary #3 fault.
Input dry contact #3 has been activated.
Warning
29
Auxiliary #4 fault.
Input dry contact #4 has been activated.
Warning
30
Auxiliary #5 fault.
Input dry contact #5 has been activated.
Warning
31
UPS shutdown by Off button on
LCD panel.
As stated.
Information
32
UPS shutdown by hardware Off
button.
As stated.
Information
33
UPS shutdown by remote user
command.
As stated.
Information
34
UPS shutdown by end of
battery backup.
The UPS was in battery mode, and the battery became
exhausted, so the UPS automatically turned itself off.
Information
35
UPS shutdown by overload.
The UPS turned itself off automatically due to a serious
overload condition.
Information
36
UPS shutdown by Emergency
Power Off.
The UPS has turned itself off due to activation of the EPO
switch.
Information
37
Actual responding modules
less than defined.
The number of power modules installed is greater than the
number of power modules defined to the UPS.
Warning
38
Static switch not responding.
As stated.
Warning
39
All UPS modules not
responding.
As stated.
Critical
40
Adapter (PC710) not
responding.
Critical
41
High load level.
The UPS is at 90% load level.
Warning
42
Detected modules are more
than defined.
More modules are installed than have been defined to the
system.
Information
1
The UPS module slots are numbered from bottom to top.