Centric Installation Guide, rel. 2.8
37
5.1.3
Current sharing
When two or more Centric units are operated in parallel, it is required that their current-sharing terminals be
connected together: yellow to yellow, orange to orange, red to red, and blue to blue. Connecting two or
more Centric units via their current-sharing terminals causes current-sharing to be take place between all
the modules of both systems together.
When
three
or more Centric units are operated in parallel, their current-sharing terminals should be
connected together as shown in Figure 31; for example:
•
connect the current-sharing terminals on UPS "X" to those on UPS "Y", AND
•
connect the current-sharing terminals on UPS "Y" to those on UPS "Z".
The parallel cable kit, supplied by Gamatronic, includes a prepared current sharing cable or cables.
Figure 31: Conceptual view of current sharing connections for 3 UPSs
Figure 32: Conceptual view of current sharing connections for 4 UPSs
When connecting current-sharing terminals, it is irrelevant which UPS is the "master" UPS and which are
the "slaves".