G
AMATRONIC
E
LECTRONIC
I
NDUSTRIES
L
TD
.
Centric Installation Guide, rel. 2.8
54
Figure 53: Verifying status of added module
11.
On the same screen ("Status > Modules"), press the Output button, select the new module
and verify that the output frequency matches the system nominal value, and that the output
voltage of each phase is within 2 % of the system nominal value.
Figure 54: Status > Modules > Output
If the output voltage of one or more phases is
not
within 2 % of the system nominal output
voltage, then:
11.1
Navigate to "Setup > Modules > Ac output voltage adjustment".
11.2
Select the new module, and adjust the problematic phases up or down as required.
11.3
Return to step 1 and repeat the verification and adjustment process until the output
voltage of each phase of the replacement module is within 2% of the system
nominal value.
12.
Navigate to the main menu screen. If the yellow, triangular "alarm" indicator is visible,
check the alarms and see if any of them are related to the new module. If there are no
related alarms, the module has been successfully added to the system. You can now
resume normal use of the UPS.