G
AMATRONIC
E
LECTRONIC
I
NDUSTRIES
L
TD
.
Centric Installation Guide, rel. 2.8
57
Figure 59: "Status > Modules" screen
8.
Unscrew the two screws that secure the module – one on the left side, one on the right side
of the front panel.
9.
Two persons are required to remove the module. Let one person stand on the left side of
the module, the other on the right side of the module. Slowly pull the module out of the
shelf.
Be prepared for the fact that when the module is completely pulled out its
weight will no longer be supported by the shelf
and will be fully in the hands of the two
workers. (Before you take the module out of the shelf, have a place where to lay it down
after it is removed.)
10.
Navigate to the main menu screen. If the yellow, triangular "alarm" indicator is visible,
check the alarms and see if any of them are related to the removal of the module. If there
are no related alarms, the module has been successfully removed from the system.You
can now resume normal use of the UPS.