14. Battery Checks
Turn the battery circuit breaker to Off and disconnect all connectors in the battery set.
Record the requested information in the following table.
Battery manufacturer
Battery model
Rating (Ah)
Number of battery strings
(x 30)
CAUTION: RISK OF EXPLOSION IF A BATTERY IS REPLACED BY AN INCORRECT
TYPE.
DO NOT DISPOSE OF BATTERIES IN A FIRE. BATTERIES MAY EXPLODE.
DO NOT DISCARD BATTERIES IN THE TRASH. THIS PRODUCT CONTAINS SEALED
LEAD-ACID BATTERIES.
FOR PROPER DISPOSAL, CONTACT YOUR LOCAL RECYCLING OR HAZARDOUS
WASTE CENTER.
Use a power resistor of 0.5
Ω
(300 W rating recommended) for the load to check the voltage drop
across the terminals of each battery. The voltage measured across the resistor should be no less
than 10 Vdc for any battery. Replace any batteries that give a reading less than 10 Vdc.
BATTERY STRING #1
BATTERY STRING #2
Batt.
no.
Good
Bad
Batt.
no.
Good
Bad
Batt.
no.
Good
Bad
Batt.
no.
Good
Bad
1
31
1
31
2
32
2
32
3
33
3
33
4
34
4
34
5
35
5
35
6
36
6
36
7
37
7
37
8
38
8
38
9
39
9
39
10
40
10
40
11
41
11
41
12
42
12
42
13
43
13
43
14
44
14
44
15
45
15
45
16
46
16
46
17
47
17
47
18
48
18
48
19
49
19
49
20
50
20
50
21
51
21
51
22
52
22
52
23
53
23
53
24
54
24
54
25
55
25
55
26
56
26
56
27
57
27
57
28
58
28
58
29
59
29
59
30
60
30
60
END OF MAINTENANCE PROCEDURES REPORT