96
CENTRIC User Guide, rel. 3.4
Figure 71: Structure of Fault_word
Table 12: Interpreting Fault_word
Bit
number
(decimal)
Hexadecimal
value when
“on”
Meaning when bit “on”
0
01
Overload
1
02
Inverter voltage
2
04
Input voltage
3
08
Dc high
4
10
Input frequency fault
5
20
Dc voltage low (battery discharged)
6
40
Input overload
7
80
IGBT desaturation
8
100
PLL without data (slave)
9
200
Inverter blackout (no voltage for 25 msec)
10
400
Inverter temperature
11
800
Inverter pulse-by-pulse (PBP) protection
12
1000
PFC temperature
13
2000
12 V_inv out of range
14
4000
12 V_PFC out of range
15
8000
Circulation