CENTRIC User Guide, rel. 3.4
Register
Variable name
GET Values
Remarks
210
4x0210 Seconds On Battery
Seconds
Only available during power failure, otherwise zero
211
4x0211 Estimated Backup Time
Minutes
Only available during power failure and when the battery is fully charged (6 in 4x0209),
otherwise zero. This value is a rough approximation received by mathematical
calculations, and assumes new and healthy batteries of average VRLA type in initial fully
charged state.
212
4x0212 Estimated Charge
0-100%
Mathematical calculation of battery charge in percents; will send 200 if no value has been
calculated
213
4x0213 DC Voltage positive
×10 Vdc
Divide the value by 10 for real measurement: 4051/10=405.1 Vdc
214
4x0214 DC Voltage Negative
×10 Vdc
Divide the value by 10 for real measurement: 4051/10=405.1 Vdc
215
4x0215 DC Voltage total
×10 Vdc
Divide the value by 10 for real measurement: 8102/10=810.2 Vdc
216
4x0216 Battery Current
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
217
4x0217 Battery Temperature
°C
Degrees centigrade
218
4x0218 Number of phases
1 to 3
Number of the UPS phases (always 3 for current units)
219
4x0219 Inverter Frequency Line 1
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
220
4x0220 Inverter Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
221
4x0221 Inverter Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
222
4x0222 Inverter Power Line 1
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
223
4x0223 Inverter Apparent Power Line 1 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
224
4x0224 Inverter Frequency Line 2
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
225
4x0225 Inverter Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
226
4x0226 Inverter Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
227
4x0227 Inverter Power Line 2
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
228
4x0228 Inverter Apparent Power Line 2 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
229
4x0229 Inverter Frequency Line 3
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
230
4x0230 Inverter Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
231
4x0231 Inverter Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
232
4x0232 Inverter Power Line 3
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
233
4x0233 Inverter Apparent Power Line 3 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
234
4x0234 Charger Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac