CENTRIC User Guide, rel. 3.4
45
Register
Variable name
GET Values
Remarks
235
4x0235 Charger Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
236
4x0236 Charger Power Line 1
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
237
4x0237 Charger Apparent Power line 1 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
238
4x0238 Charger Power factor Line 1
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
239
4x0239 Charger Load level Line 1
%
240
4x0240 Charger Voltage Line 2
×10 V
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
241
4x0241 Charger Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
242
4x0242 Charger Power Line 2
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
243
4x0243 Charger Apparent Power line 2 ×10 KVA
Divide the value by 10 for real measurement: 502/10=50.2 Hz
244
4x0244 Charger Power factor Line 2
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
245
4x0245 Charger Load level Line 2
%
246
4x0246 Charger Voltage Line 3
×10 V
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
247
4x0247 Charger Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
248
4x0248 Charger Power Line 3
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
249
4x0249 Charger Apparent Power line 3 ×10 KVA
Divide the value by 10 for real measurement: 502/10=50.2 Hz
250
4x0250 Charger Power factor Line 3
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
251
4x0251 Charger Load level Line 3
%
252
4x0252 Output Source
0: Normal
1: On Battery
2: On Bypass
3: Unknown
Unknown state can be shown when the controller can't communicate with the ST/SW
module
253
4x0253 Output Frequency
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
254
4x0254 Output Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
255
4x0255 Output Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
256
4x0256 Output Power Line 1
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
257
4x0257 Output Apparent Power Line 1 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
258
4x0258 Output Power Factor Line 1
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
259
4x0259 Output Load Line 1
%