CENTRIC User Guide, rel. 3.4
51
Register
Variable name
GET Values
Remarks
358
4x0358 Module Switching Adaptor Is
Not Responding
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
359
4x0359 Module Switching Adaptor Is
Not Switching
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
360
4x0360 More Than One Master Module
Detected
0: Alarm off
1: Alarm on
361
4x0361 AC Input Failure Page 1
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
362
4x0362 AC Input Failure Page 2
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
363
4x0363 Conflict In Nominal Settings Of
UPS Modules
0: Alarm off
1: Alarm on
When output voltage or output frequency settings are not the same on all attached UPS
modules
364
4x0364 Controller Battery Test Failed
0: Alarm off
1: Alarm on
Not available on Mega modular UPS, since there is no battery in the controller on this
model
365
4x0365 Inverter Is Out Of
Synchronization With Mains
0: Alarm off
1: Alarm on
366
4x0366 Inverter Is Out Of
Synchronization With Mains For
Short Time
0: Alarm off
1: Alarm on
367
4x0367 Controller Thread Limit
Reached
0: Alarm off
1: Alarm on
368
4x0368 Controller Memory Limit
Reached
0: Alarm off
1: Alarm on
369
4x0369 Controller Disk Space Limit
Reached
0: Alarm off
1: Alarm on