CENTRIC User Guide, rel. 3.4
L
INE
#
A
LARM MESSAGE
OR STATE OF
UPS
E
E
XPLANATION
D
EFAULT
S EVERITY
R
R
ECOMMENDED ACTION
,
IF ANY
Emergency Power Off.
R Only after the emergency situation has been resolved, the Centric can be restarted as described in section
2.7.2.1 “Restarting the UPS”.
36. UPS shutdown by end of
battery backup.
E The UPS was in battery mode, and the battery became exhausted, so the UPS automatically turned itself off.
Informational
R No action required. When normal ac input returns, battery charging will begin automatically.
37. UPS shutdown by hardware
Off button.
E The UPS was shut down by pressing the physical “OFF” button of the LCD screen.
Informational
R No action required.
38. UPS shutdown by Off button
on LCD panel.
E The UPS was shut down by pressing the OFF software button on the touch screen.
Informational
R No action required.
39. UPS shutdown by overload. E The UPS turned itself off automatically due to a serious overload condition.
Informational
R Before restarting the UPS, determine what caused the overload, and reduce the load on the UPS.
40. UPS shutdown by remote
user command.
E A user with remote access to the UPS shut the UPS down.
Informational
R No action required.