Centric Installation Guide, rel. 4.7
25
Table 3: Recommended circuit breaker / switch ratings
Note: If local electrical codes are stricter than the above recommendations, the local
codes take priority.
Table 4.1: (Icw) Rated short time withstand current and I(pk) Rated Peak short circuit value.
UPS MODEL
I(cw) [A]
I(pk) [A]
Centric 50k
575
1700
Centric 100k
1000
2500
Centric 200k
1800
3200
IMPORTANT:
Protective device must be configured to open within:
1 grid cycle
upon I (sc) ≤ 10 I(n)
4 grid cycles
upon I (sc) ≤ 5 I(n)