4.1.3 LVD battery protector
The LVD battery protector is a mechanism that protects the batteries from deep discharge. You can read
about the LVD battery protector in the User Guide.
The Battery CB trip coil must have a tripping voltage of 24 Vdc to be supplied from the system. For any
other trip coil voltages the tripping voltage will have to be provided from an external source.
The following diagram shows how to wire UPS to enable the LVD battery protector. Wire should be 12AWG
or of a cross-section area 2.5 mm
2
is recommended.
The system controller must also be configured to supply the configurable trip voltage:
1. Configure Input Dry Contact #3 to:
a. "Battery circuit breaker is off"
b. Normally closed
c. Enabled (mark with check mark)
d. Press confirm
2. Configure Output Dry Contacts #3 to:
a. LVD Battery Protector Active (mark with check mark)
b. Press confirm
3. Configure LVD battery protector
a. Enable LVD battery protector
b. Configure the desired time delay
Figure 26: LVD wiring diagram