GAMATRONIC,
A
S
OLAR
E
DGE
D
IVISION
Centric Installation Guide, rel. 4.7
48
2. Veify that the address of the empty shelf is not available.
5. Insert the new module part way.
Note: The numbering of the shelves are from bottom to top.
6.Slide the module all the way into the module shelf. Push the module inward gently but firmly to
ensure proper seating of the module’s rear connectors. Fasten the module to the UPS frame with
two screws type M5 conical, one on the left and one on the right of the module face. Verify that
the new module address is the number shelf where inserted.
7.Navigate to "Status > Modules" and select the new module. (The modules are numbered from
bottom to top). Then tap the Nominals button near the bottom of the screen, and verify that the
values for output voltage, output frequency, and frequency range match the system nominal
settings.
8. If the module was perviously shut down, navigate to "Operation > Turn on/off > Modules on".
Select the replacement module and press Confirm. (You may be prompted for the system
password.)
9.To verify that the new module is operating normally, navigate to the module status screen
("Main screen > Status > Modules"), press on the icon of the module that was just switched on,
and verify that the status is "ON" for these five items: PFC, Inverter, Dc relay, Input relay, Output
relay. Verify that the other fields are also normal.
Figure 35: Verifying status of added module
10.
On the same screen ("Status > Modules"), press the Output button, select the new module
and verify that the output frequency matches the system nominal value, and that the output
voltage of each phase is within 2 % of the system nominal value.